CONNECTION DIAGRAM

Connect the unit as in the diagram below.

EXTENSION CONNECTOR

10

17
18

1

YD

16

YB

0V

YF

15

Y9

14

Y7

13

Y5

12

Y3

11

Y1

9

YE

8

YC

7

YA

6

Y8

5

Y6

4

Y4

3

Y2

+24V

Y0

2

■ 

Output Connection Example

10

1
2

Y0

0V

+24V

+

18

YF

WIRING INSTRUCTIONS

 SOLDERLESS TERMINAL  mm (inch)

Refer  to  the  drawing  below  for  recommended  ring  tongue 
terminal size.  Spade tongue type is also applicable.  Solder-
less terminals with insulation sleeve do not fit.  Applicable 
wire size: 0.3 – 0.75 mm

2

3.2 (.13) dia.

4 min.

(.16)

12 (.47) max.

6 max. (.24)

3 (.12) max.

COMPONENT IDENTIFICATION

0 1 2 3 4 5 6 7 8 9 A B C D E F

10 11 12 13

2

3

4

1

15 16 17 18

7

8

9

6

14

5

Discrete I/O Status Indicator LED

Output Terminals

 OUTPUT TERMINAL ASSIGNMENT

 DISCRETE I/O STATUS INDICATOR LED

Discrete  I/O  modules  including  those  for  extensions  have 
LED indicators showing I/O signal status.
     

Contact ON  : LED ON

     

Contact OFF  : LED OFF

10

+24V

11

Y1

12

Y3

1

0V

2

Y0

3

Y2

13

Y5

4

Y4

14

Y7

5

Y6

15

Y9

6

Y8

16

YB

7

YA

17

YD

8

YC

9

YE

18

YF

 

NO. 

ID 

FUNCTION 

NO. 

ID 

FUNCTION

  1 

0V 

0V 

10  +24V  24V DC (common)

  2 

Y0 

Output 0 

11  Y1 

Output 1

  3 

Y2 

Output 2 

12  Y3 

Output 3

  4 

Y4 

Output 4 

13  Y5 

Output 5

  5 

Y6 

Output 6 

14  Y7 

Output 7

  6 

Y8 

Output 8 

15  Y9 

Output 9

  7 

YA  Output 10 

16  YB  Output 11

  8 

YC  Output 12 

17  YD  Output 13

  9 

YE  Output 14 

18  YF  Output 15

CONNECTING THE EXTENSION MODULE

1)  Remove the extension connector cover located at the side 

of the basic module.

2)  Connect the extension module.

3)  Mount the combined module on a DIN rail.

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Summary of Contents for R7M-EC16B

Page 1: ...be mounted inside a suitable fire enclosure This equipment is to be supplied by a Class 2 power sup ply CONFORMITY WITH EC DIRECTIVES The equipment must be mounted inside the instrument panel of a metal enclosure The actual installation environments such as panel con figurations connected devices and connected wires may affect the protection level of this unit when it is integrated in a panel syst...

Page 2: ...Indicator LED Output Terminals OUTPUT TERMINAL ASSIGNMENT DISCRETE I O STATUS INDICATOR LED Discrete I O modules including those for extensions have LED indicators showing I O signal status Contact ON LED ON Contact OFF LED OFF 10 24V 11 Y1 12 Y3 1 0V 2 Y0 3 Y2 13 Y5 4 Y4 14 Y7 5 Y6 15 Y9 6 Y8 16 YB 7 YA 17 YD 8 YC 9 YE 18 YF NO ID FUNCTION NO ID FUNCTION 1 0V 0V 10 24V 24V DC common 2 Y0 Output 0...

Page 3: ...t of the control panel Choose a thick and short cable to ground the FG terminal of the R7M module to the internal panel plate of the control panel Note If electromagnetic radiation disturbance increases by grounding the FG terminal remove the grounding When painting the internal plate of the control panel apply masking to expose metal surface to secure conductivity at the sections where the follow...

Page 4: ...nd the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small as posible Attach an electro magnetically shielded filter when noise leaks through the opening Install the R7M Series inside a control panel Attachment part of earth clamp should be fixed with screw ...

Page 5: ...ions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impact to the signal cables susceptible to the noise Ferrite core can be attached close to the cable outlet of the control panel or close to the I O terminal or connector whichever is more effective Also the imp...

Page 6: ...T AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE M SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL INCIDENTAL OR SPECIAL DAMAGES OF ANY KIND WHATSOEVER M System Co Ltd 5 2 55 Minamitsumori Nishinari ku Osaka 557 0063 JAPAN Phone 06 6659 8201 Fax 06 6659 8510 E mail info m system co jp Noise Filter M...