background image

R7M-EA8

P. 2 / 6

EM-7803-N Rev.2

CONNECTION DIAGRAM

Connect the unit as in the diagram below.

1

10

X7

9

X5

8

X3

7

X1

5

X6

4

X4

3

X2

2

X0

COM

EXTENSION CONNECTOR

■ 

Input Connection Examples

1
2

X0

COM

+

10

X7

PNP Connection

1
2

X0

COM

– +

10

X7

NPN Connection

WIRING INSTRUCTIONS

 SOLDERLESS TERMINAL  mm (inch)

Refer  to  the  drawing  below  for  recommended  ring  tongue 
terminal size.  Spade tongue type is also applicable.  Solder-
less terminals with insulation sleeve do not fit.  Applicable 
wire size: 0.3 – 0.75 mm

2

3.2 (.13) dia.

4 min.

(.16)

12 (.47) max.

6 max. (.24)

3 (.12) max.

COMPONENT IDENTIFICATION

0 1 2 3 4 5 6 7

Discrete I/O Status Indicator LED

Input Terminals

7

8

6

9 10

2

3

1

4

5

 INPUT TERMINAL ASSIGNMENT

 DISCRETE I/O STATUS INDICATOR LED

Discrete  I/O  modules  including  those  for  extensions  have 
LED indicators showing I/O signal status.
     

Contact ON  : LED ON

     

Contact OFF  : LED OFF

6

  NC

7

X1

8

X3

1

COM

2

X0

3

X2

9

X5

4

X4

10

X7

5

X6

 

NO. 

ID 

FUNCTION 

NO. 

ID 

FUNCTION

  1  COM  Common 

NC  No Connection

  2 

X0 

Input 0 

X1 

Input 1

  3 

X2 

Input 2 

X3 

Input 3

  4 

X4 

Input 4 

X5 

Input 5

  5 

X6 

Input 6 

10  X7 

Input 7

CONNECTING THE EXTENSION MODULE

1)  Remove the extension connector cover located at the side 

of the basic module.

2)  Connect the extension module.

3)  Mount the combined module on a DIN rail.

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Reviews: