R7M-DAC16C

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-7803-AK  Rev.4  P. 2 / 8

COMPONENT IDENTIFICATION

■ 

SIDE VIEW

■ 

FRONT VIEW

5

4

3

2 1 0 9

8

7

6

5

4

3

2 1 0 9

8

7

6

5

4

3

2 1 0 9

8

7

6

ERR

RD

RUN

SD

PWR

X10

X1

NODE ADD.

B.RATE

1 2 3 4 5 6 7 8

0 1 2 3 4 5 6 7

4

5

6

7

1

2

3

10 11 12 13

2

3

4

1

15 16 17 18

7

8

9

6

14

5

(A)  Status Indicator LED 
(B)  Node Address Setting Rotary SW
(C)  Baud Rate Setting Rotary SW
(D)  Operating Mode Setting DIP SW (SW1)
(E)  PC Configurator Jack
(F)  Discrete I/O Status Indicator LED
(G)  Modbus, Power Supply Terminals
(H)  I/O Terminals
( I )  Terminating Resistor SW

(A)

(G)

(H)

(B)

(C)

(D)

(E)

(F)

0 1 2 3 4 5 6 7

CNFG.

INPUT

OUTPUT

(I)Terminating Resistor SW

TERM

ON

OFF

 

STATUS INDICATOR LED

ID

COLOR FUNCTION

PWR

Red

Turns on when the internal 5V is supplied 
normally.

RUN

Red

Turns on when the refresh data is received 
normally.

ERR

Red

Turns on when the received data is abnor-
mal.

SD

Red

Turns on when the module is transmitting.

RD

Red

Turns on when the module is receiving.

 

DISCRETE I/O STATUS INDICATOR LED

LED indicators show the signal status.
  ON  : LED ON
  OFF : LED OFF

 

NODE ADDRESS

Node Address is selected between 1 and 99 in decimal.  The 
left switch determines the tenth place digit, while the right 
switch does the ones place digit of the address.

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

0

9

8

7

6

Node Address Setting (x1)

Factory setting : 00

Node Address Setting (x10)

 

BAUD RATE

Baud Rate is selected with the rotary switch.
(Factory setting: 0)

5

4

3

2

1

0

9

8

7

6

Baud Rate Setting

0: 38.4 kbps
1: 19.2 kbps
2: 9600 bps
3: 4800 bps
4: 2400 bps

5: 1200 bps
6: 14.4 kbps
7: 28.8 kbps
8: 57.6 kbps
9: 115.2 kbps

 

OPERATING MODE

(*) Factory setting

• Extension (SW1-1, 1-2)

SW1-1

SW1-2

EXTENSION

OFF

OFF

No extension (*)

ON

OFF

Discrete input 8 or 16 points

OFF

ON

Discrete output 8 or 16 points

• Output Operation Mode (SW1-3)

SW1-3

OUTPUT OPERATION MODE

OFF

Disable (*)

ON

Enable

Output switching mode can be independently selected by 
2 outputs with PC Configuration software.  An example of 
setting is given below.
  Output 0: Maintained output
  Output 1: Maintained output
  Output 2: Momentary output
  Output 3: Momentary output
  Output 4: Momentary output
  Output 5: Momentary output
  Output 6: Maintained output
  Output 7: Maintained output

• Output at the Loss of Communication (SW1-4)

SW1-4

OUTPUT AT THE LOSS OF COMMUNICATION

OFF

Reset the output (turned off)

ON

Hold the output (*) 
(maintains the last data received normally)

• Output Switching Mode (SW1-5)

SW1-5

OUTPUT SWITCHING MODE

OFF

Maintained Output Mode (*)

ON

Momentary Output Mode

SW1-5 setting is disregarded when SW1-3 is set to ON.

• Output ON Time (SW1-6, 1-7, 1-8)

SW1-6

SW1-7

SW1-8

OUTPUT ON TIME

OFF

OFF

OFF

100 ms (*)

ON

OFF

OFF

200 ms

OFF

ON

OFF

300 ms

ON

ON

OFF

500 ms

OFF

OFF

ON

1 s

ON

OFF

ON

2 s

OFF

ON

ON

5 s

ON

ON

ON

10 s

Summary of Contents for R7M-DAC16C

Page 1: ...TIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 24V DC rating 24V 10 approx 40mA GENERAL PRECAUTIONS Before you remove the unit or...

Page 2: ...s place digit of the address 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 Node Address Setting x1 Factory setting 00 Node Address Setting x10 BAUD RATE Baud Rate is selected with the rotary switch Factory...

Page 3: ...13 X5 Input 5 5 X6 Input 6 14 X7 Input 7 6 Y0 Output 0 15 Y1 Output 1 7 Y2 Output 2 16 Y3 Output 3 8 Y4 Output 4 17 Y5 Output 5 9 Y6 Output 6 18 Y7 Output 7 TERMINATING RESISTOR To use the terminating...

Page 4: ...5 20 3 12 5 5 22 DIN RAIL 35 mm wide 54 2 13 17 66 50 1 97 18 5 73 115 4 53 7 M3 SCREW TERMINALS for Modbus POWER 18 M3 SCREW TERMINALS for I O 6 24 6 24 CONNECTION DIAGRAM Note In order to improve E...

Page 5: ...OFF ON ON Y0 MOMENTARY OUTPUT MODE Y0 and Y1 Y2 and Y3 Y4 and Y5 Y6 and Y7 are respectively combined to realize momentary switching with one shot output Bit 0 2 4 6 are used to control each set of out...

Page 6: ...4 Unused 15 Unused Momentary Output Mode BIT OUTPUT DATA STATE 0 Y0 1 One shot output Y1 0 One shot output 1 Unused 2 Y2 1 One shot output Y3 0 One shot output 3 Unused 4 Y4 1 One shot output Y5 0 One...

Page 7: ...ultiple Registers General purpose register within the slave read write 17 Report Slave ID Slave type RUN status Exception Codes CODE NAME 01 Illegal Function Function code is not allowable for the sla...

Page 8: ...Rev 4 P 8 8 WIRING INSTRUCTIONS SCREW TERMINAL Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing below for recommended ring tongue terminal size Spade tongue type is also applicable Applicable w...