background image

R7L-TS4

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-7804-B  Rev.8  P. 2 / 19

COMPONENT IDENTIFICATION

ERR

SVCE

ONLINE

TX/RX

PWR

0

1

2

3

4

5

6

7

8

9

A

B

C

D

E

F

4

5

6

7

1

2

3

10 11 12 13

2

3

4

1

15 16 17 18

7

8

9

6

14

5

Reset SW

Factory Configuration Port

Service SW

Status Indicator LED

Indicator LED

L

ON

W

ORKS

, Power Supply

Terminals

Input Terminals

 

STATUS INDICATOR LED

ID

COLOR

STATE

MEANING

PWR

Green

ON

Internal 5V is normal

OFF

Internal 5V is abnormal.

ONLINE Green

ON

Online

Blink

approx.

0.5 Hz

Offline
Sending/receiving of Net-
work
Variables has stopped.

Blink

approx.

2 Hz

Receiving Wink Message

OFF

Abnormal state

ERR

Red

ON

Writing in the non-volatile 
memory

Blink

Abnormal state

OFF

Normal state

TX/RX

Green

ON

Sending/receiving Network 
Variables

OFF

Communication is lost.

SVCE

Green

ON

No network information

Blink

approx.

0.5 Hz

Offline
Sending/receiving of Net-
work
Variables has stopped.

OFF

Normal state

 

INDICATOR LED

Used to show network variable status assigned to fbLED.
     

ON  

: LED ON

     

OFF  : LED OFF

 

SERVICE SWITCH

Used to identify the node in L

ON

W

ORKS

 network configura-

tion.

 

RESET SWITCH

Used to reset the Neuron Chip.  Press the switch behind the 
front cover to reset.
Control functions are halted while completing resetting and 
restarting.  Confirm no danger before conducting resetting.

 

POWER SUPPLY, L

ON

W

ORKS

 TERMINAL ASSIGNMENT

4

NET1

5

NET2

6

U (+)

1

NET1

2

NET2

3

FG

7

V (–)

NO.

ID

FUNCTION, NOTES

1

NET1

L

ON

W

ORKS

 communication 1

2

NET2

L

ON

W

ORKS

 communication 2

3

FG

FG

4

NET1

L

ON

W

ORKS

 communication 1

5

NET2

L

ON

W

ORKS

 communication 2

6

U (+)

Power input

7

V (–)

Power input

Note:   L

ON

W

ORKS

 wiring must be paired between NET1 termi-

nals and/or NET2 terminals.

 

INPUT TERMINAL ASSIGNMENT

10

+IN0

11

–IN0

12

+IN1

1

+CJ0

2

–CJ0

3

+CJ1

13

–IN1

4

–CJ1

14

NC

5

NC

15

+IN2

6

+CJ2

16

–IN2

7

–CJ2

17

+IN3

8

+CJ3

9

–CJ3

18

–IN3

NO.

ID

FUNCTION

NO.

ID

FUNCTION

1

+CJ0 CJC 0

10 +IN0 T/C + 0

2

–CJ0 CJC 0

11 –IN0 T/C – 0

3

+CJ1 CJC 1

12 +IN1 T/C + 1

4

–CJ1 CJC 1

13 –IN1 T/C – 1

5

NC

No connection

14

NC

No connection

6

+CJ2 CJC 2

15 +IN2 T/C + 2

7

–CJ2 CJC 2

16 –IN2 T/C – 2

8

+CJ3 CJC 3

17 +IN3 T/C + 3

9

–CJ3 CJC 3

18 –IN3 T/C – 3

Summary of Contents for R7L-TS4

Page 1: ...www m system co jp POINTS OF CAUTION POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 24V AC rating 24V 10 50 60 Hz approx 85mA 24V DC rating 24V 10 approx 50mA GENERAL PRECAUTIONS Before you remove the unit or mount it turn off the power supply and input signal for safety ENVIRONMENT Indoor use When heavy...

Page 2: ... stopped OFF Normal state INDICATOR LED Used to show network variable status assigned to fbLED ON LED ON OFF LED OFF SERVICE SWITCH Used to identify the node in LONWORKS network configura tion RESET SWITCH Used to reset the Neuron Chip Press the switch behind the front cover to reset Control functions are halted while completing resetting and restarting Confirm no danger before conducting resettin...

Page 3: ...TERMINALS for LONWORKS POWER 18 M3 SCREW TERMINALS for INPUT 6 24 6 24 30 1 18 5 20 DIN RAIL 35mm wide 54 2 13 17 66 CONNECTION DIAGRAM 4 7 6 3 2 5 1 V U FG NET2 NET2 NET1 NET1 Input Connection Example INn INn CJn CJn T C CJC SENSOR 10 IN0 11 IN0 1 CJ0 2 CJ0 IN1 IN1 CJ1 CJ1 IN2 IN2 CJ2 CJ2 IN3 IN3 CJ3 CJ3 INPUT 0 12 13 3 4 INPUT 1 15 16 6 7 INPUT 2 17 18 8 9 INPUT 3 INn INn Short CJC SENSOR CJn CJ...

Page 4: ...ONNECTION HOST PC LONWORKS R7L LONWORKS R7L LONWORKS Terminator WIRING INSTRUCTIONS SCREW TERMINAL Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing below for recommended ring tongue terminal size Spade tongue type is also applicable Applicable wire size 0 25 to 1 65 mm2 AWG 22 to 16 Recommended manufacturer Japan Solderless Terminal MFG Co Ltd Nichifu Co Ltd 6 24 max 3 3 13 max mm inch ...

Page 5: ...ng Maximum sending time per fb Minimum sending time per fb Set Tag No name Indicate Model No and Version Indicate Serial No NodeObject Network Variables Configuration Properties Network Variables NETWORK VARIABLE TYPE Range Default EXPLANATIONS nviRequest SNVT_obj_request For use with LonMaker and other tools nvoStatus SNVT_obj_status For use with LonMaker and other tools nvoFileDirectory SNVT_add...

Page 6: ...0 0 0 Maximum time interval to send network variables per fb Power supply must be reset when this configuration prop erty is changed Network variables are sent out in the specified intervals even when there is no change in the value No sending when a value less than 10 0 is set Invalid property when the assigned fb has no network vari ables to be sent to the network SCPTminSendTime Number of fb SN...

Page 7: ...CNTOut Set the maximum count Set the value when fbCNT is reset fbCNT SCPTdirection nviCNTIn SCPTinvrtOut nviCNTCtrl SCPTpwrUpState nvoCNTOut SCPTnvType SCPTmaxRnge SCPTsetpoint Network Variables Configuration Properties Network Variables NETWORK VARIABLE TYPE Range Default EXPLANATIONS nviCNTIn SNVT_switch 0 0 0 100 0 1 Invalid 0 0 0 Counted object nviCNTCtrl SNVT_switch 0 0 0 100 0 1 Invalid 0 0 ...

Page 8: ...1 Count always reset to 0 Bit 5 8 through 15 Invalid Minimum input pulse width 500 ms for nviCNTIn 50 ms for the input terminals DO NOT connect a network variable to nviCNTIn when one of the input terminals other than nviCNTIn is assigned as the counted object ON time per 1 second increments SCPTinvrtOut nviCNTIn SNVT_lev_disc ST_OFF ST_ON ST_OFF Count logic at nviCNTIn ST_OFF Count with nvoCNTIn ...

Page 9: ... and 100 setpoints Zero adjustment Span adjustment fbTS SCPTsceneNmbr nvoTSVal SCPTnvType SCPTminDeltaTemp SCPToffset SCPTdefScale SCPTsetpoint nvoTSPVal SCPToffset SCPTgain Network Variables Configuration Properties Thermocouple input Input 0 Input 1 Input 2 Input 3 nv 60 nv 63 nv 64 nv 67 Network Variables NETWORK VARIABLE TYPE Range Default EXPLANATIONS nvoTSVal SNVT_temp 274 0 6279 5 0 0 SNVT_...

Page 10: ...set 1 SCPToffset 0 SCPTdefScale nvoTSVal SNVT_lev_percent 80 000 120 000 0 0 Gain applied to SCPToffset 0 SCPTsetpoint 0 nvoTSVal Same as nvoTSVal nvoTSVal lower range temperature SCPTsetpoint 0 SCPTsetpoint 1 SCPTsetpoint 1 nvoTSVal Same as nvoTSVal nvoTSVal upper range temperature SCPTsetpoint 0 SCPTsetpoint 1 SCPToffset nvoTSPVal SNVT_lev_percent 163 840 163 835 0 0 nvoTSPVal zero offset adjust...

Page 11: ...ariable type 0 and 100 setpoints Network variable type 0 and 100 setpoints nviCVIn SCPTnumDigits SCPTnvType SCPTsetpoint nvoCVOut SCPTnvType SCPTsetpoint Network Variables Configuration Properties Network Variables NETWORK VARIABLE TYPE Range Default EXPLANATIONS nviCVIn SNVT_lev_percent 163 840 163 835 0 0 SNVT_temp 274 0 6279 5 0 0 SNVT_temp_p 273 17 327 66 0 0 SNVT_count_32 0 999 999 999 0 Inpu...

Page 12: ...that of the source when using 60 63 SCPTnvType nviCVIn SNVT_nv_type SNVT_temp Indicates nviCVIn type For use with LonMaker and other tools SCPTnvType nvoCVOut SNVT_nv_type SNVT_temp Indicates nvoCVOut type For use with LonMaker and other tools SCPTsetpoint 0 nviCVIn Same as nviCVIn Scaling setting Output SCPTsetpoint 0 nvoCVOut is provided with the input SCPTsetpoint 0 nviCVIn Output SCPTsetpoint ...

Page 13: ...S nviARMIn SNVT_lev_percent 163 840 163 835 0 0 SNVT_temp 274 0 6279 5 0 0 SNVT_temp_p 273 17 327 66 0 0 SNVT_count_32 0 999 999 999 0 Inputs the value to be compared to the alarm setpoint nvoARM1 SNVT_switch 0 0 0 100 0 1 0 0 1 nviARMIn alarm 1 HH 100 0 1 with nviARMIn SCPTsetpoint 0 Reset to 0 0 0 from 100 0 1 with nviARMIn SCPTsetpoint 0 SCP Toffset nvoARM2 SNVT_switch 0 0 0 100 0 1 0 0 1 nviAR...

Page 14: ...ARMIn SNVT_nv_type SNVT_lev_percent Indicates nviARMIn type For use with LonMaker and other tools SCPTsetpoint 0 nviARMIn SNVT_lev_percent 163 840 163 835 80 000 SNVT_temp 274 0 6279 5 80 0 SNVT_temp_p 273 17 327 66 80 00 SNVT_count_32 0 999 999 999 10 000 Alarm 1 nvoARM1 setpoint SCPTsetpoint 1 nviARMIn SNVT_lev_percent 163 840 163 835 60 000 SNVT_temp 274 0 6279 5 60 0 SNVT_temp_p 273 17 327 66 ...

Page 15: ... nv 97 nviLEDIn01 SNVT_switch nv 98 nviLEDIn02 SNVT_switch nv 99 nviLEDIn03 SNVT_switch nv 112 nviLEDIn16 SNVT_switch Network Variables Configuration Properties Network Variables NETWORK VARIABLE TYPE Range Default EXPLANATIONS nviLEDState SNVT_state 0 or 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 The front LEDs 0 F turn on off according to the input Bit 0 through Bit 15 assigned to LED 0 through F respect...

Page 16: ...riables Configuration Properties Extension discrete output Y0 Y2 Y4 Y6 Y8 YA YC YE Output nviDOEX1 status Y1 Y3 Y5 Y7 Y9 YB YD YF Output nviDOEX2 status nv 4 nv 11 nviDOEX1 SNVT_switch nv 12 nv 19 nviDOEX2 SNVT_switch Output Terminal v s fbDOEX Network Variables nviDOEX1 nviDOEX2 Assignments FUNCTIONAL BLOCK NETWORK VARIABLE OUTPUT TERMINAL fbDOEX 0 nviDOEX1 Y0 nviDOEX2 Y1 fbDOEX 1 nviDOEX1 Y2 nvi...

Page 17: ...on or off Y1 Y3 Y5 Y7 Y9 YB YD YF of the extension module depending upon this input 100 0 1 ON Other OFF Configuration Properties CONFIGURATION PROPERTY NETWORK VARIABLE TYPE Range Default EXPLANATIONS SCPTdirection SNVT_state 0 or 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 1 Output held or not at power off 0 OFF at the power startup 1 Outputs the held status at the power startup Bit 0 Bit 2 through 15...

Page 18: ...X8 XA XC XE X1 X3 X5 X7 X9 XB XD XF Normal Mode Status output at nvoDIEX1 Status output at nvoDIEX2 Combination Mode Refer to the table in the next page fbDIEX SCPTdirection nvoDIEX1 SCPTinvrtOut nvoDIEX2 SCPTinvrtOut Set operating mode Invert output Invert output Input Terminal v s fbDIEX Network Variables nvoDIEX1 nvoDIEX2 Assignments FUNCTIONAL BLOCK NETWORK VARIABLE INPUT TERMINAL fbDIEX 0 nvo...

Page 19: ...4 X6 X8 XA XC XE X1 X3 X5 X7 X9 XB XD XF nvoDIEX1 nvoDIEX2 OFF OFF 0 0 0 OFF Invalid ON OFF 100 0 1 ON Invalid OFF ON 0 0 0 OFF 0 0 0 OFF ON ON 100 0 1 ON 100 0 1 ON nvoDIEX2 SNVT_switch 0 0 0 100 0 1 Invalid 0 0 0 Configuration Properties CONFIGURATION PROPERTY NETWORK VARIABLE TYPE Range Default EXPLANATIONS SCPTdirection SNVT_state 0 or 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Bit 0 Bit 1 fbDIEX opera...

Reviews: