R7L-TS4
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-7804-B Rev.8 P. 19 / 19
■
FUNCTIONAL BLOCK: fbDIEX[0...7]
• Network Variables
Normal Mode
NETWORK
VARIABLE
TYPE
{ Range }
{ Default }
EXPLANATIONS
nvoDIEX1
{SNVT_switch}
{0.0 0}, {100.0 1}, {Invalid}
{0.0 0}
Outputs X0, X2, X4, X6, X8, XA, XC, XE status of the extension module
nvoDIEX2
{SNVT_switch}
{0.0 0}, {100.0 1}, {Invalid}
{0.0 0}
Outputs X1, X3, X5, X7, X9, XB, XD, XF status of the extension module
Combination Mode
NETWORK
VARIABLE
TYPE
{ Range }
{ Default }
EXPLANATIONS
nvoDIEX1
{SNVT_switch}
{0.0 0}, {100.0 1}, {Invalid}
{0.0 0}
Contact input, nvoDIEX1 and nvoDIEX2 Reference Table
X0
X2
X4
X6
X8
XA
XC
XE
X1
X3
X5
X7
X9
XB
XD
XF
nvoDIEX1
nvoDIEX2
OFF
OFF
0.0 0 (OFF)
Invalid
ON
OFF
100.0 1 (ON)
Invalid
OFF
ON
0.0 0 (OFF)
0.0 0 (OFF)
ON
ON
100.0 1 (ON) 100.0 1 (ON)
nvoDIEX2
{SNVT_switch}
{0.0 0}, {100.0 1}, {Invalid}
{0.0 0}
• Configuration Properties
CONFIGURATION
PROPERTY
NETWORK
VARIABLE
TYPE
{ Range }
{ Default }
EXPLANATIONS
SCPTdirection
----
{SNVT_state}
{0 or 1}
{0,0,0,0,0,0,0,0,
0,0,0,0,0,0,0,0}
Bit 0, Bit 1: fbDIEX operating mode
0,0 : Normal mode
0,1 : Combination mode
Bit 2 through 15 : Invalid
SCPTinvrtOut
nvoDIEX1
{SNVT_lev_disc}
{ST_OFF, ST_ON}
{ST_OFF}
Contact input logic is inverted at nvoDIEX1.
ST_OFF : OFF at open contact, ON at closed contact
ST_ON : ON at open contact, OFF at closed contact
SCPTinvrtOut
nvoDIEX2
{SNVT_lev_disc}
{ST_OFF, ST_ON}
{ST_OFF}
Contact input logic is inverted at nvoDIEX2.
ST_OFF : OFF at open contact, ON at closed contact
ST_ON : ON at open contact, OFF at closed contact