background image

R7G4HH-A-YVF4

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-7777-F  Rev.2  P. 3 / 9

 

OPERATING MODE

(*) Factory setting

• Output Range: SW1-3, 1-4, 1-5, 1-6

SW1-3

SW1-4

SW1-5

SW1-6

OUTPUT RANGE

OFF

OFF

OFF

OFF

-10 – +10V DC (*)

ON

OFF

OFF

OFF

-5 – +5V DC

OFF

ON

OFF

OFF

-1 – +1V DC

ON

ON

OFF

OFF

0 – 10V DC

OFF

OFF

ON

OFF

0 – 5V DC

ON

OFF

ON

OFF

1 – 5V DC

OFF

ON

ON

OFF

0 – 1V DC

ON

ON

ON

OFF

-0.5 – +0.5V DC

ON

ON

ON

ON

PC Configurator setting

OUTPUT RANGE

• 

Wide span

:  -10 – +10V DC, -5 – +5V DC, 0 – 10V DC,  

 

0 – 5V DC, 1 – 5V DC

• 

Narrow span

: -1 – +1V DC, 0 – 1V DC, -0.5 – +0.5V DC

• Output at the Loss of Communication: SW1-7

SW1-7

OUTPUT AT THE LOSS OF COMMUNICATION

OFF

Hold the output (*)
(Hold the last received normal data.)

ON

Output reset value 
(Output is fixed to the output reset value.)

• Transfer Rate: SW1-8

SW1-8

TRANSFER RATE

OFF

12Mbps (*)

ON

6Mbps

Note: Be sure to set unused SW1-1 and 1-2 to OFF.

 

TERMINATING RESISTOR

To use the terminating resistor, turn the switch ON, and 
OFF to invalidate.  (Factory setting OFF)

 

POWER SUPPLY TERMINAL ASSIGNMENT

4

NC

5

6

7

1

2

3

NC

24V 0V

NC

NC

FE

1. 

NC

2. 

NC

3. 

FE

4. 

NC

5. 

NC

6. 

+24V

7. 

0V

-
-
Functional earth
-
-
Power supply (24V DC)
Power supply (0V)

 

OUTPUT TERMINAL ASSIGNMENT

14

5

6

NC

VL1 COM2

15

VH2

16

17

18

7

8

9

NC

VH3

NC

VL2 COM3

10

1

2

NC

NC COM0

11

VH0

12

13

3

4

NC

VH1

VL0 COM1

VL3

NO.

ID

FUNCTION

NO.

ID

FUNCTION

1

NC

No connection

10

NC No connection

2

COM0 Common 0

11

VH0 Wide span volt. 0

3

VL0 Narrow span volt. 0 12

NC No connection

4

COM1 Common 1

13

VH1 Wide span volt. 1

5

VL1 Narrow span volt. 1 14

NC No connection

6

COM2 Common 2

15

VH2 Wide span volt. 2

7

VL2 Narrow span volt. 2 16

NC No connection

8

COM3 Common 3

17

VH3 Wide span volt. 3

9

VL3 Narrow span volt. 3 18

NC No connection

Summary of Contents for R7G4HH-A-YVF4

Page 1: ...to ensure the CE conform ity POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 24V DC rating 24V DC 10 appr...

Page 2: ...ormal Turns off when the internal power is abnormal RUN Green Turns on when the refresh data is received normally Turns off when no communication or communication error ERR Red Turns off when output c...

Page 3: ...ed to the output reset value Transfer Rate SW1 8 SW1 8 TRANSFER RATE OFF 12Mbps ON 6Mbps Note Be sure to set unused SW1 1 and 1 2 to OFF TERMINATING RESISTOR To use the terminating resistor turn the s...

Page 4: ...f duplex communication 12345678 12345678 1 NC 2 NC 3 NC 4 TR 5 TR 6 NC 7 NC 8 SLD Unused Unused Unused Network Network Unused Unused Shield Full duplex communication Communication connector pin assign...

Page 5: ...move the upper hook of the unit from the DIN rail 1 2 3 DIN RAIL MOUNTING RIGHT ANGLE Mounting 1 Insert the longer DIN rail mounter slider until it clicks twice as shown below 1 2 Set the upper hook a...

Page 6: ...F Rev 2 P 6 9 TERMINAL CONNECTIONS Connect the unit as in the diagram below EXTERNAL DIMENSIONS unit mm inch 130 5 12 140 5 51 152 5 98 4 16 50 1 97 5 2 4 16 4 5 18 dia 6 18 M3 Output terminal screws...

Page 7: ...3 17 8 9 VH3 VL3 COM3 13 VH1 VL1 COM1 4 5 15 VH2 VL2 COM2 6 7 4 5 3 6 PAIR WIRING Ethernet cable pin assignment 4 5 6 7 8 2 3 NC TXD TR 1 NC RXD NC RXD NC NC SLD TXD TR 4 5 6 7 8 2 3 NC 1 NC NC SLD 6...

Page 8: ...ELD Full duplex communication Half duplex communication MASTER CONNECTION Terminating Resistor MOUNTING REQUIREMENTS unit mm inch 140 5 51 2 M4 WIRING INSTRUCTIONS TORQUE Wiring screw for separable te...

Page 9: ...gurable with the configurator software model R7CFG Refer to the software manual for details ADD n ADD n ADD n 2 ADD n 1 ADD n 4 ADD n 2 ADD n 6 ADD n 3 Data is represented in 16 bit binary Negative va...