CHECKING ETHERNET/IP CONNECTION

 

IP ADDRESS

Set the host address in the IP address using the front rotary switches.
When using the host address in the IP address set on the PC configurator software (model:R7CFG), set the switches to ‘00H’.
When the network address, Subnet Mask, and Default Gateway need to be changed, do so on R7CFG.

 

CHECK WIRING

Connect an Ethernet cable to the front RJ-45 modular jack.
To configure a DLR (Device Level Ring) network, perform wiring so as to form a ring topology.
The DLR network requires at least one node as a ring supervisor.
The customer shall prepare one or more ring supervisors separately as the R7G4HEIP unit does not function as one.

 

CHECK LED

When wiring is correct, LNK1 or LNK2 is turned on.

 

CHECK R7G4HEIP CONNECTION

Enter “ping command” on the Windows MS-DOS as follows:

    C:¥WINDOWS>ping ***.***.***.***
    (***.***.***.***: Enter IP address in decimal.)

    ping ***.***.***.*** with 32 bytes of data:
    Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64
    Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64
    Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64
    Reply from ***.***.***.*** : bytes=32 time<10ms TTL=64

    Ping statistics for ***.***.***.***
    Packets:Sent=4,Received=4,Lost=0(0% loss)

Replies in case of normal connection are as shown above.  If the connection cannot be established normally due to e.g. wrong 
IP address, other replies such as “time over” will be received.

 

CHECK CONNECTION TO THE APPLICATION SOFTWARE

Check Point 1: LINK LED

LNK1 or LNK2 turns on when the module has established normal connections with PC, PLC, hub, and so on, regardless of 
data sending/receiving status.
In the case that they are not on, check power supply to the hub.

Check Point 2: MS AND NS INDICATOR

When the module has transmitted/received data correctly to/from the application software, MS and NS indicators turn on in 
green.

I/O DATA DESCRIPTION

0

15

Input 0
Input 1
Input 2
Input 3

0: OFF   1:  ON

Input 7

 DISCRETE INPUT

0

Output 0
Output 1
Output 2
Output 3

0: OFF   1: ON

Output 7

 DISCRETE OUTPUT

15

Summary of Contents for R7F4HEIP-DAC16C

Page 1: ...protective measures to ensure the CE conform ity POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 24V DC rating 24V 10 approx 70mA GENERAL PRECAUTIONS Before you remove the unit or mount it turn off the power supply and input signal for safety Before you remove the terminal block or mount it make sure to t...

Page 2: ... the signal status ON LED ON OFF LED OFF IP ADDRESS Set the host address 2 digit hexadecimal number in the IP address using rotary switches SA1 and SA2 for the first digit and the second digit respectively When using the host address in the IP address set on the PC configurator software model R7CFG set the switches to 00H When the network address Subnet Mask and Default Gateway need to be changed ...

Page 3: ... 46 47 48 49 50 51 52 PIN No ID FUNCTION PIN No ID FUNCTION 1 24V1 24V DC 27 24V2 24V DC 2 X0 Input 0 28 Y0 Output 0 3 24V1 24V DC 29 24V2 24V DC 4 GND1 0V 30 GND2 0V 5 X2 Input 2 31 Y2 Output 2 6 24V1 24V DC 32 24V2 24V DC 7 GND1 0V 33 GND2 0V 8 X4 Input 4 34 Y4 Output 4 9 24V1 24V DC 35 24V2 24V DC 10 GND1 0V 36 GND2 0V 11 X6 Input 6 37 Y6 Output 6 12 24V1 24V DC 38 24V2 24V DC 13 GND1 0V 39 GND...

Page 4: ...move the upper hook of the unit from the DIN rail 1 2 3 SURFACE MOUNTING 1 Insert the two DIN rail mounter sliders until it clicks once as shown below 1 1 2 Mount the unit with M4 screws referring to the External Dimensions Torque 1 4 N m DIN RAIL MOUNTING RIGHT ANGLE Mounting 1 Insert the longer DIN rail mounter slider until it clicks twice as shown below 2 Set the upper hook at the rear side of ...

Page 5: ...mm wide 2 4 3 dia 4 deep CONNECTION DIAGRAM Note In order to improve EMC performance bond the FE terminal to ground Caution FE terminal is NOT a protective conductor terminal 1 The network cable can be connected to either one 1 EtherNet IP RJ 45 MODULAR JACK 1 EtherNet IP RJ 45 MODULAR JACK 3 4 2 25 26 24 1 14 29 30 28 51 52 50 27 40 4 5 1 24V DC FE 0V 24V1 X7 GND1 24V2 Y0 GND2 24V2 Y7 GND2 24V1 G...

Page 6: ... software model R7CFG Refer to the users manual of the software for detailed operations CHANNEL BATCH SETTING PARAMETER SETTING RANGE DEFAULT SETTING Conversion rate 1 ms 5 ms 10 ms 20 ms 50 ms 70 ms 100 ms 200 ms 10 ms Output Hold Clear Hold Clear Hold ETHERNET SETTING PARAMETER SETTING RANGE DEFAULT SETTING IP Address 0 0 0 0 255 255 255 255 192 168 0 250 Subnet Mask 0 0 0 0 255 255 255 255 255 ...

Page 7: ...ing command on the Windows MS DOS as follows C WINDOWS ping Enter IP address in decimal ping with 32 bytes of data Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Ping statistics for Packets Sent 4 Received 4 Lost 0 0 loss Replies in case of normal connection are as shown above If the connection can...

Reviews: