R7F4HC-DA32-K

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8009-A  P. 2 / 7

COMPONENT IDENTIFICATION

Terminator DIP SW

Discrete Input

Status Indicator LED

A20

B20

A1

B1

SW1

Power

Error

RD

1 2 3 4

×10

×1

STATION ADD.

SLD

FE

2

1

DB

3

DG

4

DA

5

NC

NC

4

5

FE1

3

PWR-

2

PWR+

1

Run

SD

Connector for Power Supply

CC-Link Connector

Input Connector

Station Address

Setting Rotary SW

Operation Mode Setting
DIP SW (SW1)

Status Indicator LED

 TOP VIEW

 FRONT VIEW

 

STATUS INDICATOR LED

ID

STATUS COLOR FUNCTION

Power

ON

Green

Internal 5V power is in normal 
status.

Run

ON

Green

The refresh data is received 
normally

Error

ON

Red

The received data is abnormal.

SD

ON

Green

The module is transmitting.

RD

ON

Green

The module is receiving.

 

DISCRETE INPUT STATUS INDICATOR LED

Green LED shows the input status.
  ON : LED ON
  OFF : LED OFF

 

STATION ADDRESS

The left switch determines the tenth place digit, while the 
right one does the ones place digit of the station address 
(1 - 64).
(Factory setting: 00)

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

0

9

8

7

6

Station Address Setting (x1)

Station Address Setting (x10)

 

OPERATING MODE

(*) Factory setting

• Read Rate (SW1-1, 1-2, 1-3)

BAUD RATE

SW1

1

2

3

0

156 kbps (*)

OFF

OFF

OFF

1

625 kbps

ON

OFF

OFF

2

2.5 Mbps

OFF

ON

OFF

3

5 Mbps

ON

ON

OFF

4

10 Mbps

OFF

OFF

ON

Note: Be sure to set unused SW1-4 to OFF.

 

TERMINATING RESISTOR

To use the terminating resistor, turn the switch ON, and 
OFF to invalidate. (Factory setting OFF)

Summary of Contents for R7F4HC-DA32-K

Page 1: ...for the power source input and output connected to the unit etc POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated...

Page 2: ...e refresh data is received normally Error ON Red The received data is abnormal SD ON Green The module is transmitting RD ON Green The module is receiving DISCRETE INPUT STATUS INDICATOR LED Green LED...

Page 3: ...ationship to the pin number of the unit Wire according to the instruction manual of the unit INPUT SENSOR EXC ASSIGNMENT Unit side conector FCN 365P040 AU Fujitsu Cable side connector FCN 36 J040 AU F...

Page 4: ...from the DIN rail A C B DIN RAIL MOUNTING RIGHT ANGLE Mounting A Insert the longer DIN rail mounter slider until it clicks twice as shown below A B Set the upper hook at the rear side of the unit on t...

Page 5: ...6 6659 8201 Fax 81 6 6659 8510 E mail info m system co jp EM 8009 A P 5 7 TERMINAL CONNECTIONS Connect the unit as in the diagram below EXTERNAL DIMENSIONS unit mm inch 115 4 53 55 2 17 72 2 83 123 4...

Page 6: ...tion FE1 terminal is NOT a protective conductor terminal B10 B6 B7 B8 B9 B5 A17 A18 A19 A20 A16 A12 A13 A14 A15 A11 A7 A8 A9 A10 A6 B4 B1 B2 A5 B3 A1 A2 A3 A4 B20 B16 B17 B18 B19 B15 B11 B12 B13 B14 X...

Page 7: ...1F F Unused Refresh Data Y 0 1F I O DATA DESCRIPTIONS DISCRETE INPUT 0 15 Input 0 Input 16 Input 1 Input 17 Input 2 Input 18 Input 3 Input 19 Input 15 Input 31 0 OFF 1 ON 0 OFF 1 ON 0 OFF 1 ON 0 OFF...

Reviews: