R7C-YV4

EM-7801-AD  P. 5 / 9

COMMUNICATION CABLE CONNECTIONS

Master Unit

DA
DB

DG

SLD

FE

Remote Unit

DA
DB

DG

SLD

FE

Remote Unit

TERMINATOR

TERMINATOR

blue

white

yellow

Be sure to connect the terminating resistor across DA and DB at both ends of communication line.
When this unit is located at an end, turn the terminating resistor SW ON.
The Master Unit can be located at not only both ends but also any node of the of communication line.

   

MASTER CONNECTION

DA
DB

DG

SLD

FG

DATA ALLOCATION

Unused

Unused

Unused

Unused

RWrn+0

+1

+2

+3

Analog output 0

Analog output 1

Analog output 2

Analog output 3

RWwn+0

+1

+2

+3

Interval-timed Response (X)

Refresh Data (Y)

   

ANALOG OUTPUT

I/O DATA DESCRIPTIONS

0

15

16-bit binary data
Negative values represented in 2

s complements

■ 

ANALOG OUTPUT

WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.5 N·m

 

SOLDERLESS TERMINAL

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm

2

 (AWG 22 to 16)

Recommended manufacturer: Japan Solderless Terminal 
MFG. Co., Ltd, Nichifu Co., Ltd

6 (.24) max

3.3 (.13) max

mm (inch)

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Summary of Contents for R7C-YV4

Page 1: ...OPERATIONAL RANG Locate the power input rating marked on the product and confirm its operational range as indicated below 24V AC rating 24V 10 50 60Hz approx 180mA 24V DC rating 24V 10 approx 90mA GEN...

Page 2: ...ss Setting x10 BAUD RATE Baud Rate is selected with the rotary switch 5 4 3 2 1 0 9 8 7 6 Baud Rate Setting 0 156 kbps 1 625 kbps 2 2 5 Mbps 3 5 Mbps 4 10 Mbps OPERATING MODE Factory setting Output at...

Page 3: ...addressed to the station due to noise interference Missing parts of the data sent from the master ON OFF OFF OFF OFF Unable to receive data due to wire breakdown ON OFF ON OFF ON OFF Faulty Baud Rate...

Page 4: ...LS for OUTPUT 6 24 50 1 97 6 24 18 5 73 115 4 53 DIN RAIL 35mm wide 5 20 30 1 18 54 2 13 17 66 CONNECTION DIAGRAM 4 7 6 3 2 5 1 V U FG SLD DG DB DA OUTPUT 0 In order to improve EMC performance bond th...

Page 5: ...ON Unused Unused Unused Unused RWrn 0 1 2 3 Analog output 0 Analog output 1 Analog output 2 Analog output 3 RWwn 0 1 2 3 Interval timed Response X Refresh Data Y ANALOG OUTPUT I O DATA DESCRIPTIONS 0...

Page 6: ...hick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out of the control panel Choose a thick and short cable to ground the FG terminal of the R7C module to...

Page 7: ...he panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small as...

Page 8: ...s are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impact to the...

Page 9: ...Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cover and ground it to the internal panel plate using an earth clamp To connect...