background image

R7C-YV4

EM-7801-AD  P. 2 / 9

COMPONENT IDENTIFICATION

5

4

3

2 1 0 9

8

7

6

5

4

3

2 1 0 9

8

7

6

5

4

3

2 1 0 9

8

7

6

ERR

RD

RUN

SD

PWR

X10

X1

STATION ADD.

B.RATE

CNFG.

1 2 3 4 5 6 7 8

4

5

6

7

1

2

3

2

3

4

1

5

10

7

8

9

6

(A)  Status Indicator LED 

*

1

(B)  Station Address Setting Rotary SW
(C)  Baud Rate Setting Rotary SW
(D)  Operating Mode Setting DIP SW (SW1)
(E)  PC Configurator Jack
(F)  CC-Link, Power Supply Terminals
(G)  Output Terminals
(H)  Terminating Resistor SW

*

1. Refer to ‘Status Indicator LED’ section for detailed information.

(A)

(F)

(G)

(B)

(C)

(D)

(E)

TERM

ON

OFF

■ 

SIDE VIEW

■ 

FRONT VIEW

(H)

 

STATUS INDICATOR LED

ID

COLOR FUNCTION

PWR

Red

Turns on when the internal 5V is sup-
plied normally.

RUN

Red

Turns on when the refresh data is re-
ceived normally.

ERR

Red

Turns on when the received data is 
abnormal.

SD

Red

Turns on when the module is transmit-
ting.

RD

Red

Turns on when the module is receiving.

 

STATION ADDRESS

Station Address is selected between 1 and 64 in decimal.
The left switch determines the tenth place digit, while the
right switch does the ones place digit of the address.

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

0

9

8

7

6

Station Address Setting (x1)

Station Address Setting (x10)

 

BAUD RATE

Baud Rate is selected with the rotary switch.

5

4

3

2

1

0

9

8

7

6

Baud Rate Setting

0 : 156 kbps
1 : 625 kbps
2 : 2.5 Mbps
3 : 5 Mbps
4 : 10 Mbps

 

OPERATING MODE

(*) Factory setting

• Output at the loss of communication (SW1-4)

SW1-4 OUTPUT AT THE LOSS OF COMMUNICATION

OFF

Reset the output (to -15% or approx. -11.5V DC)

ON

Hold the output (*)
(maintains the last data received normally)

• Output range (SW1-5, 1-6, 1-7, 1-8)

SW1-5 SW1-6 SW1-7 SW1-8

OUTPUT RANGE

OFF

OFF

OFF

OFF

-10 – +10V DC (*)

ON

OFF

OFF

OFF

-5 – +5V DC

ON

ON

OFF

OFF

0 – 10V DC

OFF

OFF

ON

OFF

0 – 5V DC

ON

OFF

ON

OFF

1 – 5V DC

ON

ON

ON

ON

PC Configurator setting

Note : Be sure to set unused SW1-1 through 1-3 to OFF.

 

POWER SUPPLY, CC-LINK TERMINAL ASSIGNMENT

4

DA

5

DG

6

U(+)

1

DB

2

SLD

3

FG

7

V(–)

NO.

ID

FUNCTION, NOTES

1

DB

White

2

SLD

Shield

3

FG

FG

4

DA

Blue

5

DG

Yellow

6

U(+)

Power input

7

V(–)

Power input

 

OUTPUT TERMINAL ASSIGNMENT

10

5

6

1

2

7

8

9

3

4

V3

COM3

NC

NC COM0

V0

V1

V2

COM1 COM2

NO.

ID

FUNCTION

NO.

ID

FUNCTION

1

NC

No connection

6

NC

No connection

2 COM0 Common 0

7

V0

Voltage output 0

3 COM1 Common 1

8

V1

Voltage output 1

4 COM2 Common 2

9

V2

Voltage output 2

5 COM3 Common 3

10

V3

Voltage output 3

 

TERMINATING RESISTOR

To use the terminating resistor, turn the switch ON, and
OFF to invalidate.  (Factory setting OFF)

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Summary of Contents for R7C-YV4

Page 1: ...OPERATIONAL RANG Locate the power input rating marked on the product and confirm its operational range as indicated below 24V AC rating 24V 10 50 60Hz approx 180mA 24V DC rating 24V 10 approx 90mA GEN...

Page 2: ...ss Setting x10 BAUD RATE Baud Rate is selected with the rotary switch 5 4 3 2 1 0 9 8 7 6 Baud Rate Setting 0 156 kbps 1 625 kbps 2 2 5 Mbps 3 5 Mbps 4 10 Mbps OPERATING MODE Factory setting Output at...

Page 3: ...addressed to the station due to noise interference Missing parts of the data sent from the master ON OFF OFF OFF OFF Unable to receive data due to wire breakdown ON OFF ON OFF ON OFF Faulty Baud Rate...

Page 4: ...LS for OUTPUT 6 24 50 1 97 6 24 18 5 73 115 4 53 DIN RAIL 35mm wide 5 20 30 1 18 54 2 13 17 66 CONNECTION DIAGRAM 4 7 6 3 2 5 1 V U FG SLD DG DB DA OUTPUT 0 In order to improve EMC performance bond th...

Page 5: ...ON Unused Unused Unused Unused RWrn 0 1 2 3 Analog output 0 Analog output 1 Analog output 2 Analog output 3 RWwn 0 1 2 3 Interval timed Response X Refresh Data Y ANALOG OUTPUT I O DATA DESCRIPTIONS 0...

Page 6: ...hick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out of the control panel Choose a thick and short cable to ground the FG terminal of the R7C module to...

Page 7: ...he panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small as...

Page 8: ...s are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impact to the...

Page 9: ...Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cover and ground it to the internal panel plate using an earth clamp To connect...