background image

R7C-EA16

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-7801-I  Rev.6  P. 4 / 7

CONFORMITY WITH CE MARKING

 

CE MARKING

CE marking requires to integrate safety regulations existed in each country in EU territory and to secure smooth distribution 
of products of which safety is guaranteed.  It is mandatory by law that products distributed and sold in EU territory to have 
CE mark which shows that the product conforms with the requirements of EU Directive.  Each EU Directive describes the 
scope of apparatuses to which that EU Directive is applied.  M-System’s R7C must conform with EMC Directive.
Each Directive states only basic requirements.  In order to mark the CE on an assembled machinery equipment, its manufac-
turer needs to check the overall conformity with Directives applicable to it.

 

WARNINGS AND CAUTIONS WHEN INSTALLING THE R7C

The R7C needs to be installed in a control panel.  This is effective not only to ensure general safety but also to contain noise 
emissions by the R7C inside the control panel.  We conduct a series of testing to see that the product conforms to EMC Direc-
tive while it is installed in the control panel.
Warning and cautions when installing R7C are stated below.

• Use control panels with an internal panel plate, both made of metal, when installing the R7C.
• Make sure to adequately ground the control panel and the internal panel plate with a thick cable to maintain low imped-

ance at high frequency.

• Use shielded cables for the signals taken out of the control panel.
• Choose a thick and short cable to ground the FG terminal of the R7C module to the internal panel plate of the control panel.

    Note: If electromagnetic radiation disturbance increases by grounding the FG terminal, remove the grounding.

• When painting the internal plate of the control panel, apply masking to expose metal surface to secure conductivity at the 

sections where the following parts are attached:

  - Bolts attaching the internal panel to the control panel
  - Ground for the FG of the R7C module
  - Earth clamp on the shielded cable

• Noise emissions inside the control panel might leak through its openings.  Design them as small as possible.  Recommended 

diameter is 10 cm or less.

Supplement:

Additional measures may be taken depending upon actual installation sites.  These points of cautions are illustrated in the 
next page.

• Prevent noise leakage by wrapping cables using shield covers, shield tubes and flexible conduits etc. if noise leaks through 

the cable outlet.

• Use an electromagnetic shield gasket and block up the gap between the control panel cabinet and its cover, if noise leaks 

through it.

• Connecting the internal panel plate and the cover of the control panel to the main cabinet using an earth strap may be 

effective to strengthen the grounding.

• Electromagnetically shielded control panel cabinet is effective for shielding.

Summary of Contents for R7C-EA16

Page 1: ...s equipment must be mounted inside a suitable fire enclosure This equipment is to be supplied by a Class 2 power sup ply CONFORMITY WITH EU DIRECTIVES The equipment must be mounted inside the instrument panel of a metal enclosure The actual installation environments such as panel con figurations connected devices connected wires may af fect the protection level of this unit when it is integrated i...

Page 2: ... ID FUNCTION NO ID FUNCTION 1 COM Common 10 NC No Connection 2 X0 Input 0 11 X1 Input 1 3 X2 Input 2 12 X3 Input 3 4 X4 Input 4 13 X5 Input 5 5 X6 Input 6 14 X7 Input 7 6 X8 Input 8 15 X9 Input 9 7 XA Input 10 16 XB Input 11 8 XC Input 12 17 XD Input 13 9 XE Input 14 18 XF Input 15 CONNECTING THE EXTENSION MODULE 1 Remove the extension connector cover located at the side of the basic module 2 Conn...

Page 3: ... X2 2 X0 COM EXTENSION CONNECTOR Input Connection Examples 1 2 X0 COM 18 XF PNP Connection 1 2 X0 COM 18 XF NPN Connection WIRING INSTRUCTIONS SCREW TERMINAL Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing below for recommended ring tongue terminal size Spade tongue type is also applicable Applicable wire size 0 25 to 1 65 mm2 AWG 22 to 16 Recommended manufacturer Japan Solderless Terminal...

Page 4: ...ing the R7C Make sure to adequately ground the control panel and the internal panel plate with a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out of the control panel Choose a thick and short cable to ground the FG terminal of the R7C module to the internal panel plate of the control panel Note If electromagnetic radiation disturbance increases...

Page 5: ... using an electro magnetically shielded control panel By connecting the internal panel plate and the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small as posible Attach an electro magnetically shielded filter when noise leaks through the opening Install th...

Page 6: ... Additional measures may be taken depending upon actual installation sites These points of cautions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impact to the signal cables susceptible to the noise Ferrite core can be attached close to the cable outlet of the c...

Page 7: ...m is not effective Points of cautions applicable when wiring the R7C Series To external apparatus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cover and ground it to the internal panel plate using an earth clamp To connect with apparatuses outside the control panel via CC Link ground the cable shield using an earth clamp K...

Reviews: