background image

R7C-EA16

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-7801-I  Rev.6  P. 2 / 7

COMPONENT IDENTIFICATION

0

1

2

3

4

5

6

7

8

9

A

B

C

D

E

F

10 11 12 13

2

3

4

1

15 16 17 18

7

8

9

6

14

5

Discrete Input Status Indicator LED

Input Terminals

 

DISCRETE INPUT STATUS INDICATOR LED

LED indicators show the signal status.
  ON  : LED ON
  OFF : LED OFF

 

INPUT TERMINAL ASSIGNMENT

10

NC

11

X1

12

X3

1

COM

2

X0

3

X2

13

X5

4

X4

14

X7

5

X6

15

X9

6

X8

16

XB

7

XA

17

XD

8

XC

9

XE

18

XF

NO.

ID

FUNCTION

NO.

ID

FUNCTION

1

COM Common

10

NC

No Connection

2

X0

Input 0

11

X1

Input 1

3

X2

Input 2

12

X3

Input 3

4

X4

Input 4

13

X5

Input 5

5

X6

Input 6

14

X7

Input 7

6

X8

Input 8

15

X9

Input 9

7

XA

Input 10

16

XB

Input 11

8

XC

Input 12

17

XD

Input 13

9

XE

Input 14

18

XF

Input 15

CONNECTING THE EXTENSION MODULE

1) Remove the extension connector cover located at the side 

of the basic module.

2) Connect the extension module.

3) Mount the combined module on a DIN rail.

TERMINAL CONNECTIONS

Connect the unit as in the diagram below.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

11.5

(.45)

10 11 12 13

2

3

4

1

15 16 17 18

7

8

9

6

14

5

94 (3.70)

30 (1.18)

[5 (.20)]

DIN RAIL

35mm wide

54 (2.13)

17 (.66)

18–M3 SCREW 

TERMINALS

for INPUT

6 (.24)

3 (.12)

5.5 (.22)

50 (1.97)

18.5 (.73)

Summary of Contents for R7C-EA16

Page 1: ...s equipment must be mounted inside a suitable fire enclosure This equipment is to be supplied by a Class 2 power sup ply CONFORMITY WITH EU DIRECTIVES The equipment must be mounted inside the instrument panel of a metal enclosure The actual installation environments such as panel con figurations connected devices connected wires may af fect the protection level of this unit when it is integrated i...

Page 2: ... ID FUNCTION NO ID FUNCTION 1 COM Common 10 NC No Connection 2 X0 Input 0 11 X1 Input 1 3 X2 Input 2 12 X3 Input 3 4 X4 Input 4 13 X5 Input 5 5 X6 Input 6 14 X7 Input 7 6 X8 Input 8 15 X9 Input 9 7 XA Input 10 16 XB Input 11 8 XC Input 12 17 XD Input 13 9 XE Input 14 18 XF Input 15 CONNECTING THE EXTENSION MODULE 1 Remove the extension connector cover located at the side of the basic module 2 Conn...

Page 3: ... X2 2 X0 COM EXTENSION CONNECTOR Input Connection Examples 1 2 X0 COM 18 XF PNP Connection 1 2 X0 COM 18 XF NPN Connection WIRING INSTRUCTIONS SCREW TERMINAL Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing below for recommended ring tongue terminal size Spade tongue type is also applicable Applicable wire size 0 25 to 1 65 mm2 AWG 22 to 16 Recommended manufacturer Japan Solderless Terminal...

Page 4: ...ing the R7C Make sure to adequately ground the control panel and the internal panel plate with a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out of the control panel Choose a thick and short cable to ground the FG terminal of the R7C module to the internal panel plate of the control panel Note If electromagnetic radiation disturbance increases...

Page 5: ... using an electro magnetically shielded control panel By connecting the internal panel plate and the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small as posible Attach an electro magnetically shielded filter when noise leaks through the opening Install th...

Page 6: ... Additional measures may be taken depending upon actual installation sites These points of cautions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impact to the signal cables susceptible to the noise Ferrite core can be attached close to the cable outlet of the c...

Page 7: ...m is not effective Points of cautions applicable when wiring the R7C Series To external apparatus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cover and ground it to the internal panel plate using an earth clamp To connect with apparatuses outside the control panel via CC Link ground the cable shield using an earth clamp K...

Reviews: