background image

R6N-RS2

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-7781-BK  Rev.3  P. 3 / 4

TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

102 (4.02)

7.5 (.30)

*

Screwdriver stem diameter: 6 mm (.24”) or less

102 (4.02)

8–M3

SCREW TERMINAL

WIRE INSERTION ANGLE

: approx. 35°

SCREWDRIVER 

*

INSERTION ANGLE

       : approx. 55°

5

6

7

8

1

2

3

4

 

CONNECTION DIAGRAM

BUS CONNECTOR

3

1

2

7

5

6

INTERNAL

POWER 

INTERNAL

BUS

INPUT 1

INPUT 2

A

B

B

RTD

A

B

B

RTD

• Unused Input Channels

Close across the unused input terminals with a resistor as 
shown below and set the DIP switch for Pt 100 input.

1

2

INPUT 1

5

6

INPUT 2

100Ω

3

7

If a resistor is not connected to unused input terminals, sta-
tus indicator LED blinks in red (0.5 sec. cycle), and a burn-
out flag is set in the PLC or the host device.

WIRING INSTRUCTIONS

 

SCREW TERMINAL

Torque: 0.5 N·m

 

SOLDERLESS TERMINAL  unit: mm (inch)

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.
Solderless terminals with insulation sleeve do not fit.
Applicable wire size: 0.2 – 2.5 mm

2

3.2 (.13) dia.

4 min.

(.16)

5.8 max.

(.23)

5.5 max.
 (.22) 