COMPONENT IDENTIFICATION
RUN LED
4 5 6
1 2 3
ON
1
T/C
Burnout
Temp. Unit
2 3 4 5 6 7 8
Function
Euro Type
Connector Terminals
RUN
■
SIDE VIEW
■
FRONT VIEW
■
STATUS INDICATOR LED
RUN indicator
: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
■
SIDE DIP SW
(*) Factory setting
• Thermocouple Type: SW1, 2, 3, 4
SW
T/C
1
2
3
4
OFF
OFF
OFF
OFF
(PR)
ON
OFF
OFF
OFF
K (CA) (*)
OFF
ON
OFF
OFF
E (CRC)
ON
ON
OFF
OFF
J (IC)
OFF
OFF
ON
OFF
T (CC)
ON
OFF
ON
OFF
B (RH)
OFF
ON
ON
OFF
R
ON
ON
ON
OFF
S
OFF
OFF
OFF
ON
C (WRe 5-26)
ON
OFF
OFF
ON
N
OFF
ON
OFF
ON
U
ON
ON
OFF
ON
L
OFF
OFF
ON
ON
P (Platinel II)
• Temperature Unit: SW5, 6
SW
TEMP. UNIT
5
6
OFF
OFF
°C (*)
ON
OFF
°F
OFF
ON
K (Absolute Temp)
• Burnout: SW7, 8
SW
BURNOUT
7
8
INPUT 1
INPUT 2
OFF
OFF
Downscale
ON
ON
Upscale (*)
PC CONFIGURATOR
With configurator software, settings shown below are available.
Refer to the software manual of R5CON for detailed operation.
■
CHANNEL INDIVIDUAL SETTING
PARAMETER
AVAILABLE RANGE
DEFAULT SETTING
Zero Scale
-32000 to +32000
0
Full Scale
-32000 to +32000
10000
Bias [Zero Adj.]
-320.00 to +320.00
0.00
Gain [Span Adj.]
-32000 to +32000
1.0000
Zero Base
Depends on sensor type
0.00
Full Base
Depends on sensor type
0.00
■
CHANNEL BATCH SETTING
PARAMETER
AVAILABLE RANGE
DEFAULT SETTING
Limit (V1.00 or higher)
No check mark: Limits to the scaling values equivalent to -15 % to
+115 %.
Check-marked: Limits within Zero Scale to Full Scale.
No check mark