R3-SV8A
P. / 3
EM-84 Rev.4
■
STATUS INDICATOR LED
RUN indicator
: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator
: Bi-color (red/green) LED;
Red with the input circuit abnormality (AD
converter response failure);
Green in normal operating conditions.
■
SIDE DIP SW
• Input Range
: SW1, SW2 (selectable per 4 channels)
INPUT 1 through INPUT 4 (SW1)
RANGE
INPUT 5 through INPUT 8 (SW2)
1
2
3
4
OFF
OFF
OFF
OFF
-100 – +100mV (*)
ON
OFF
OFF
OFF
-50 – +50mV
OFF
ON
OFF
OFF
0 – 100mV
ON
ON
OFF
OFF
0 – 60mV
OFF
OFF
ON
OFF
0 – 50mV
ON
OFF
ON
OFF
-60 – +60mV
• Conversion Rate
: SW3
SW
CONVERSION RATE
160 ms (
*
)
80 ms
40 ms
20 ms
SW3-1
OFF
ON
OFF
ON
SW3-2
OFF
OFF
ON
ON
(*)Factory setting
SW2
SW1
ON
1
2
3
4
5
6
7
8
ON
ON
1
2
3
4
5
6
7
8
SW3
1
2
3
4
5
19
20
21
22
15
16
17
18
23
24
25
26
27
28
6
7
8
9
10
11
12
13
14
1
2
3
4
■
FRONT VIEW
ERR LED
RUN LED
■
SIDE VIEW
Range
Input 1-4 (SW1)
or
Input 5-8 (SW2)
Conv.
Rate
Functions
COMPONENT IDENTIFICATION