EM-8389 Rev.7 P. 4 / 6
COUNTER SETTING FROM HOST PC/PLC
■
COUNTER RESET
(Available for R3-NC1, R3-NC3, R3-NE1, R3-NM1, R3-NDx, R3-NFL1, R3-NP1, R3-NML3 (Firmware version 2.00 or later))
Setting SW3-4 OFF and turning power on enable the function.
The bits indicating the channels to reset counter are allocated in the first word from host PC/PLC.
When these bits are changed from 0 to 1, the counter is reset. When it is confirmed that the counter is reset, return to 0.
Notice that if the bit remains at 1, the next reset will not work.
0
15
Count reset CH.1
Count reset CH.16
Count reset CH.2
Count reset CH.3
Count reset CH.4
■
COUNTER PRESET
(Available in combination with R3-NE1, R3-NM1 (Firmware version 2.00 or later), and R3-PA16 displayed ‘SW3-4 RESET/
PRESET’ on the right side)
Setting SW3-4 ON and turning power on enable the function.
Write the preset value to the Holding Resisters, which has same address as the Input Resisters.
• Input Resisters
• Holding Resisters
Address
n+0
n+1
n+2
n+3
n+14
n+15
Input 1
Input 3
Input 15
Input 2
Input 4
Input 16
Address
n+0
n+1
n+2
n+3
n+14
n+15
Preset value of Input 1
Preset value of Input 3
Preset value of Input 15
Preset value of Input 2
Preset value of Input 4
Preset value of Input 16