R3-PA16

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8389  Rev.7  P. 4 / 6

COUNTER SETTING FROM HOST PC/PLC

 

COUNTER RESET

(Available for R3-NC1, R3-NC3, R3-NE1, R3-NM1, R3-NDx, R3-NFL1, R3-NP1, R3-NML3 (Firmware version 2.00 or later))
Setting SW3-4 OFF and turning power on enable the function.
The bits indicating the channels to reset counter are allocated in the first word from host PC/PLC.
When these bits are changed from 0 to 1, the counter is reset.  When it is confirmed that the counter is reset, return to 0.
Notice that if the bit remains at 1, the next reset will not work.

0

15

Count reset CH.1

Count reset CH.16

Count reset CH.2
Count reset CH.3
Count reset CH.4

 

COUNTER PRESET

(Available in combination with R3-NE1, R3-NM1 (Firmware version 2.00 or later), and R3-PA16 displayed ‘SW3-4 RESET/
PRESET’ on the right side) 
Setting SW3-4 ON and turning power on enable the function.
Write the preset value to the Holding Resisters, which has same address as the Input Resisters.

• Input Resisters

• Holding Resisters

Address

n+0

n+1

n+2

n+3

n+14

n+15

Input 1

Input 3

Input 15

Input 2

Input 4

Input 16

Address

n+0

n+1

n+2

n+3

n+14

n+15

Preset value of Input 1

Preset value of Input 3

Preset value of Input 15

Preset value of Input 2

Preset value of Input 4

Preset value of Input 16