COMPONENT IDENTIFICATION

RUN LED

1

11
12
13
14
15
16
17
18
19
20

2
3
4
5
6
7
8
9

10

ERR LED

Status Indicator LED

9

10

11

12

13

14

15

16

1

2

3

4

5

6

7

8

■ 

FRONT VIEW

■ 

SIDE VIEW

SW3

ON

4

3

2

1

Count Reset

Count Reset Input

Set the Count Reset SW to OFF to start counting.

Functions

Count Setting
from Host PC/PLC

 

STATUS INDICATOR LED

RUN indicator:

 Bi-color (red/green) LED; 

Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.

ERR indicator

: Bi-color (red/green) LED;

Red with excitation abnormality;
Green in normal operating conditions.

Input status indicator

: Red LED; turns on with the input 

ON.

 

SIDE DIP SW

(*)Factory setting

• Count Reset: SW3-1

SW

COUNT RESET

NORMAL

COUNT RESET

SW3-1

OFF (*)

ON

Note: Be sure to turn OFF during use.

• Count Reset Input: SW3-3

SW

COUNT RESET INPUT

INVALID

VALID

SW3-3

OFF (*)

ON

• Count Setting from Host PC/PLC: SW3-4

SW

COUNT SETTING FROM HOST PC/PLC

COUNT RESET

COUNT PRESET

SW3-4

OFF (*)

ON

(For option /PRS, count preset is ON)
Note : Be sure to set unused SW3-2 to OFF.

PC CONFIGURATOR

With configurator software, settings shown below are available.
Refer to the software manual of R3CON for detailed operation.

• Max. Pulse count: 1 to 65,535 (factory setting: 10,000)
• Totalized count value (V2.01 or higher)
• Accumulated pulse count (Pulse counts are changeable by using the PC Configurator, refer to “Counter setting from host 

PC/ PLC” section hereafter.)