R3-NE1

P. 6 / 8

EM-836 Rev.3

ADDRESS

DATA TYPE

DATA

Coil (0X)

1 – 1024

Digital Output (discrete output)

Inputs (1X)

1 – 1024

Digital Input (discrete input)

1025 – 1040

Module Status

1041 – 1056

Error Status

1057 – 1072

Data Error Status

Input Registers (3X)

1 – 256

I

Analog Input

257 – 768

F

Analog Input

Holding Registers (4X)

1 – 256

I

Analog Output

257 – 768

F

Analog Output

I: Integer, 0 – 10000 (0 – 100%)
F: Floating (32-bit data cannot be accessed using floating addresses.)
Note: DO NOT access addresses other than mentioned above.  Such access may cause problems such as inadequate opera-
tion.

• 

Module Status indicates whether individual I/O module are mounted or not.  The bit corresponding to the mounted slots 

turns to “1,” and the unmounted slots to “0.”

• 

Error Status indicates error status for each module as described below.  The bit corresponding to such modules turns to 

“1.”
  R3-TSx, R3-RSx, R3-US4:  Input burnout
  R3-DA16A:   

 

Power input in error or disconnected

  R3-YSx:  

 

 

Output current error (e.g. load unconnected)

• 

Data Error Status indicates overrange (R3-US4: out of -10% to +110%; the other types: out of -15% to +115%) status for 

each module.  The bit corresponding to such modules turns to “1.”

Modbus I/O ASSIGNMENTS

TRANSMISSION DATA ASSIGNMENTS

The DIP SW located at the side of the module specifies each I/O module’s data allocation (occupied data area).
For example, when the data areas are assigned as shown below:
      Module 1 

 

4

      Module 2 

 

4

      Module 3 

 

4

      Module 4 

 

1

      Module 5 

 

1

      Module 6 

 

1

      Module 7 

 

1

Then the I/O data are assigned as in the table below:

ADDRESS

POSITION

Input Registers (3X)

Holding Registers (4X)

1 – 4, 257 – 264

Slot 1

5 – 8, 265 – 272

Slot 2

9 – 12, 273 – 280

Slot 3

13, 281 – 282

Slot 4

14, 283 – 284

Slot 5

15, 285 – 286

Slot 6

16, 287 – 288

Slot 7

ADDRESS

POSITION

Coil (0X)

Inputs (1X)

1 – 64

Slot 1

65 – 128

Slot 2

129 – 192

Slot 3

193 – 208

Slot 4

209 – 224

Slot 5

225 – 240

Slot 6

241 – 256

Slot 7

For Coil (0X) and Inputs (1X), addresses 16 times assigned 
data areas (Data Allocation Type) are allotted with the 
Data Allocation Type ‘1’ and ‘4.’  With ‘8’ and ‘16,’ 64 (4 

×

 

16) are automatically assigned.

Summary of Contents for R3-NE1

Page 1: ...se When heavy dust or metal particles are present in the air install the unit inside proper housing with sufficient ven tilation Do not install the unit where it is subjected to continuous vibration D...

Page 2: ...2 5 SW2 6 7 SW2 7 SW2 8 8 SW SETTTING DATA ALLOCATION OFF OFF 1 ON OFF 4 OFF ON 8 ON ON 16 Refer to the specifications of the related series for the Data Allocation Type of I O modules Dual Communicat...

Page 3: ...able Solder less terminals with insulation sleeve do not fit Applicable wire size 0 75 1 25 mm2 3 2 13 dia 4 min 16 12 47 max 6 max 24 3 12 max 1 2 3 4 5 6 130 5 12 27 5 1 08 109 4 29 POSITIONING GUID...

Page 4: ...Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Ping statistics for Packets Sent 4 Received 4 Lost 0 0 loss Replies in case of normal co...

Page 5: ...l output from the slave 16 Preset Multiple Registers X General purpose register within the slave 17 Report Slave ID X Slave type RUN status 18 Program 884 M84 19 Reset Comm Link 20 Read General Refere...

Page 6: ...r or disconnected R3 YSx Output current error e g load unconnected Data Error Status indicates overrange R3 US4 out of 10 to 110 the other types out of 15 to 115 status for each module The bit corresp...

Page 7: ...the data For example 135 4 F is con verted into 135 Minus temperature is converted into negative values represented in 2 s complements ACCUMULATED COUNT DATA 32 bit data models R3 PA2 PA4A WT1 WT4 et...

Page 8: ...warranty To submit a claim under this warranty the purchaser must return at its expense the defective M System product to the below address together with a copy of its original sales invoice THIS IS...

Reviews: