background image

R3-NE1

P.  / 8

EM-836 Rev.3

COMPONENT IDENTIFICATION

SW2

ON

8

7

6

5

4

3

2

1

SW3

ON

4

3

2

1

ON

8

7

6

5

4

3

2

1

SW1

1
2
3

4
5
6

5

4 3 2 1

0

9

8

7

6

5

4 3 2 1

0

9

8

7

6

RUN LED

■ 

FRONT VIEW

■ 

SIDE VIEW

ERR LED

RJ-45 Modular Jack

Not used

Not used

Configuration Jack

Functions

LINK

DPLX (Duplex)

LINK10 (10Mbps)

LINK100

(100Mbps)

COL (Collision)

 SIDE DIP SW

• Data Allocation

: SW1, SW2

Data Allocation Type* must be assigned to each I/O mod-
ule position to specify how many data areas (four types) 
are to be occupied by each.
Two bits from SW1 and SW2 are assigned to each posi-
tion, and data areas can be specified from the module No. 1 
through 8.  Setting for No. 9 and later modules is identical 
to No. 8.

SW ASSIGNMENT

MODULE NO.

SW1-1

SW1-2

1

SW1-3

SW1-4

2

SW1-5

SW1-6

3

SW1-7

SW1-8

4

SW2-1

SW2-2

5

SW2-3

SW2-4

6

SW2-5

SW2-6

7

SW2-7

SW2-8

8

SW SETTTING

DATA ALLOCATION

OFF

OFF

1

ON

OFF

4

OFF

ON

8

ON

ON

16

*Refer to the specifications of the related series for the 
Data Allocation Type of I/O modules.

• Dual Communication

: SW3

When two network modules are mounted, one must be  
‘Main’ (OFF) network and the other must be  ‘Sub’ (ON) 
network.  For single communication, the network module 
must always be set to  ‘Main’ (OFF). 

SW

DUAL COMMUNICATION

MAIN (

*

)

SUB

SW3-1

OFF

ON

• Input Error Data

: SW3

Hold:

 When the communication from an input module is 

lost due to the input module error, the network module 
holds the signal and stands by until the communication 
recovers.

Set to ‘0’:

 When the communication from an input module 

is lost due to the input module error, the network module 
outputs ‘0.’

SW

INPUT ERROR DATA

HOLD (

*

)

SET 

 ‘0’

SW3-2

OFF

ON

• LED Function

: SW3

Functions assigned to the front RUN and ERR LEDs can 
be selected.

SW3-4

LED

RUN

ERR

OFF (*) Green when normal

Green when abnormal

ON

Red when receiving

Red when transmitting

(*) Factory setting

Summary of Contents for R3-NE1

Page 1: ...se When heavy dust or metal particles are present in the air install the unit inside proper housing with sufficient ven tilation Do not install the unit where it is subjected to continuous vibration D...

Page 2: ...2 5 SW2 6 7 SW2 7 SW2 8 8 SW SETTTING DATA ALLOCATION OFF OFF 1 ON OFF 4 OFF ON 8 ON ON 16 Refer to the specifications of the related series for the Data Allocation Type of I O modules Dual Communicat...

Page 3: ...able Solder less terminals with insulation sleeve do not fit Applicable wire size 0 75 1 25 mm2 3 2 13 dia 4 min 16 12 47 max 6 max 24 3 12 max 1 2 3 4 5 6 130 5 12 27 5 1 08 109 4 29 POSITIONING GUID...

Page 4: ...Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 time 10ms TTL 64 Ping statistics for Packets Sent 4 Received 4 Lost 0 0 loss Replies in case of normal co...

Page 5: ...l output from the slave 16 Preset Multiple Registers X General purpose register within the slave 17 Report Slave ID X Slave type RUN status 18 Program 884 M84 19 Reset Comm Link 20 Read General Refere...

Page 6: ...r or disconnected R3 YSx Output current error e g load unconnected Data Error Status indicates overrange R3 US4 out of 10 to 110 the other types out of 15 to 115 status for each module The bit corresp...

Page 7: ...the data For example 135 4 F is con verted into 135 Minus temperature is converted into negative values represented in 2 s complements ACCUMULATED COUNT DATA 32 bit data models R3 PA2 PA4A WT1 WT4 et...

Page 8: ...warranty To submit a claim under this warranty the purchaser must return at its expense the defective M System product to the below address together with a copy of its original sales invoice THIS IS...

Reviews: