EM-8355  Rev.15  P. 7 / 8

 

BCD DATA (32-bit data, models: R3-BA32A, BC32A, etc.)

32-bit binary data is used for BCD.
Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn.

0

15

+0

Lower 16 bits

0

15

+1

Higher 16 bits

 

DISCRETE DATA (models: R3-DA16 and DC16, etc.)

0

15

Input 1   (Output 1)
Input 2   (Output 2)
Input 3   (Output 3)
     :               :
Input 16 (Output 16)

0 : OFF
1 : ON 

 

PLC REDUNDANT SYSTEM (models: R3-NC1-x/W) 

Bit 0 of RY(n+1) is assigned to designate control system or standby system.  Set this bit from the host PLC to switch from the 
PLC master control system to the standby system, or vice versa.  The R3 module output (slave station) is controlled according 
to the bit combinations as shown in the table below.  No switching is required for the R3 input modules which continuously 
send out data to both ‘main’ and ‘sub’ network modules.
  RY(n+1) 0 = 0 : PLC master control system
  RY(n+1) 0 = 1 : PLC standby system

R3 MAIN (RY(n+1) 0)

R3 SUB (RY(n+1) 0)

CONTROL

0

0

Output from the ‘main’ network module.

0

1

Output from the ‘main’ network module.

1

0

Output from the ‘sub’ network module.

1

1

Hold the output

• Operation 

RY (n+1) 0 = 1

Communication Status

Start

Break

Restored

Switching by PLC

RY (n+1) 0 = 0

R3 main network

RY (n+1) 0 = 1

RY (n+1) 0 = 0

R3 sub network

(1)

(2)

(3)

(4)

(5)

1) When the PLC master control/standby system bit is undefined due to no communication, the both host PLCs function as 

‘standby’ system for each of R3 ‘main’ and ‘sub’ network modules.  All contact outputs are off, and analog output modules 

output -15%.

2) The master PLC communicates with the R3 main network module, while the standby PLC communicates with the R3 sub 

network module.

3) When a wire breakdown is detected at the R3 main network, the output signal is held for the preset time period (Timer is 

programmable with the PC Configurator Software, R3CON).  After the time has been elapsed, the output is switched from 

the R3 main to R3 sub network.  Be sure to set an appropriate output signal to the R3 sub network before the switching.  

The host PLC for the R3 main network is now functioning as standby system.

4) Once the PLC control is transferred to the standby system, it is necessary to set RY(n+1) 0 = 1 to the R3 main network in 

order to prevent R3 output control automatically switched to the main network when the R3 main network is restored.  If 

it is set to RY(n+1) 0 = 0, the R3 output will be switched to the main network even when the PLC control is in the standby 

system.

5) When both R3 main and R3 sub network modules are in communication, the output can be switched without delay by set-

ting RY(n+1) 0 values.  Be sure to set an appropriate output signal to the network module before the control is switched to 

it.

Summary of Contents for R3-NC1

Page 1: ...Hz approx 20VA 24V DC rating 24V 10 approx 12W GENERAL PRECAUTIONS DO NOT set the switches on the module while the power is supplied The switches are used only for maintenance without the power ENVIRONMENT Indoor use When heavy dust or metal particles are present in the air install the unit inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuou...

Page 2: ...ough 8 Setting for No 9 and later modules is identical to No 8 SW ASSIGNMENT MODULE NO SW1 1 SW1 2 1 SW1 3 SW1 4 2 SW1 5 SW1 6 3 SW1 7 SW1 8 4 SW2 1 SW2 2 5 SW2 3 SW2 4 6 SW2 5 SW2 6 7 SW2 7 SW2 8 8 SW SETTING DATA ALLOCATION OFF OFF 1 ON OFF 4 OFF ON 8 ON ON 16 Refer to the specifications of the related series for the Data Allocation Type of I O modules Dual Communication SW3 1 When two network m...

Page 3: ...M Note In order to improve EMC performance bond the FG terminal to ground Caution FG terminal is NOT a protective conductor terminal INTERNAL POWER INTERNAL BUS DG DB DA SLD FG To Other CC Link Devices CONFIGURATION JACK JACK BUS CONNECTOR Not provided with No Power Supply type module 1 4 RUN RUN RUN CONTACT OUTPUT 2 3 6 U V FG POWER INPUT WIRING INSTRUCTIONS M3 SCREWTERMINAL power input RUN conta...

Page 4: ...the data sent from the master to the network module OUTPUT DATA The figure below shows the allocation of the data sent from the network module to the master INPUT DATA The figure below shows the allocation of the data sent from the master to the network module Sixteen 16 data areas are available Total data areas occupied by I O modules must be within this limitation The DIP SW located at the side ...

Page 5: ... mod ule turns to 1 R3 TSx R3 RSx R3 US4 Input burnout R3 DA16A Power input in error or disconnected R3 YSx Output current error e g load unconnected R3 PC16A External power supply in error or disconnected Data Error Status RX n 2 0 through RX n 2 F indicate overrange R3 US4 out of 10 to 110 the other types out of 15 to 115 status for each module The bit corresponding to such module turns to 1 RX ...

Page 6: ...nge represented in 2 s complement 0 15 TEMPERATURE DATA 16 bit data models R3 RS4 TS4 and US4 etc 16 bit binary data With C temperature unit raw data is multiplied by 10 For example 25 5 C is converted into 255 With F temperature unit the integer section of raw data is directly converted into the data For example 135 4 F is con verted into 135 Minus temperature is converted into negative values re...

Page 7: ...PLC RY n 1 0 0 R3 main network RY n 1 0 1 RY n 1 0 0 R3 sub network 1 2 3 4 5 1 When the PLC master control standby system bit is undefined due to no communication the both host PLCs function as standby system for each of R3 main and sub network modules All contact outputs are off and analog output modules output 15 2 The master PLC communicates with the R3 main network module while the standby PL...

Page 8: ...the Master Unit X0020 Only when required Number of connected modules Number of retries Number of automatic return modules Operation specification when the CPU is down Reserved station specification X002F M0 M1 PLS M0 SET M1 RST M1 MOV D0 MOV D1 MOV D2 T0 H0002 H0001 D0 K3 T0 H0002 H0006 D3 K1 MOV D3 M1 MOV D13 MOV D T0 H0002 H0020 D13 K M1 MOV D4 MOV D5 MOV D6 MOV D7 MOV D8 MOV D9 MOV D10 MOV D11 ...

Reviews: