PC CONFIGURATOR
The following parameter items can be set with using PC Configurator Software (model: R3CON).
Refer to the users manual for the R3CON for detailed operation of the software program.
■
NETWORK MODULE SETTING
PARAMETER
SETTING RANGE
DEFAULT SETTING
Time (no communication time)
0.2 – 3200.0 (sec.)
3.0 (sec.)
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■
EXTERNAL DIMENSIONS unit: mm (inch)
1
2
3
4
5
6
130 (5.12)
27.5 (1.08)
109 (4.29)
POSITIONING
GUIDE
TERMINAL
COVER
6–M3
SCREW
6.2
(.24)
■
CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG
terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.
INTERNAL POWER
INTERNAL BUS
DG
DB
DA
SLD
FG
To Other
CC-Link
Devices
CONFIGURATION JACK
JACK
BUS CONNECTOR
*
Not provided with ‘No Power Supply’ type module.
1
4
RUN
+
RUN
–
RUN CONTACT OUTPUT
2
3
6
U (+)
V (–)
FG
POWER INPUT
*
*
WIRING INSTRUCTIONS
■
M3 SCREW TERMINAL (power input, RUN contact output)
Torque: 0.5 N·m
■
SOLDERLESS TERMINAL
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable. Solder-
less terminals with insulation sleeve do not fit.
Recommended manufacturer: Japan Solderless Terminal
MFG.Co.Ltd, Nichifu Co.,ltd
Applicable wire size: 0.75 to 1.25 mm
2
12max
6max
3max
4min
3.2 dia.
(mm)
■
EURO TYPE CONNECTOR TERMINAL (CC-Link)
Applicable wire size: 0.2 to 2.5 mm
2
(AWG24 to 12)
Stripped length: 7 mm