• CC-Link Ver.1.10
1. Module Status
RX (n + 0) 0 indicates whether a virtual I/O module is specified or not.
The virtual I/O module is a fixed one for CC-Link Ver.1.10, the related bit must be “1”.
RX (n + 0) 0 Virtual I/O module 1
2. RX (n + 1) to RX (n + 6) are not used.
3. RX (n + 7) 0 to RX (n + 7) 7 is a reservation area.
RX (n + 7) B is used as Ready signal, the bit is “1” when R3-GC1 is in normal.
RX (n + 7) 8 to A, C to F are not used.
• CC-Link Ver.2.00
1. Module Status
RX (n + 0) 0 to RX (n + 0) 7 indicates whether virtual I/O modules are specified or not.
When a virtual module is specified, the related bit is “1”. When a virtual module is not specified, the related bit is “0”.
The detailed information is as shown below.
RX (n + 0) 0 Virtual I/O module 1
RX (n + 0) 1 Virtual I/O module 2
RX (n + 0) 2 Virtual I/O module 3
RX (n + 0) 3 Virtual I/O module 4
RX (n + 0) 4 Virtual I/O module 5
RX (n + 0) 5 Virtual I/O module 6
RX (n + 0) 6 Virtual I/O module 7
RX (n + 0) 7 Virtual I/O module 8
2. RX (n + 1) to RX (n + m * 7 – 2) are not used.
3. RX (n + m * 7 – 1) 0 to RX (n + m * 7 – 1) 7 is a reservation area.
RX (n + m * 7 – 1) B is used as Ready signal, the bit is “1” when R3-GC1 is in normal.
RX (n + m * 7 – 1) 8 to A, C to F are not used.