EM-2436    P. 7 / 8

COMMUNICATION CABLE CONNECTIONS

 

WIRING CONNECTION WITH SLAVE DEVICES

DA
DB

DG

SLD

FE

DA
DB

DG

SLD

FE

DA
DB

DG

SLD

FE

Remote Unit

Remote Unit

TERMINATOR

TERMINATOR

*

2

*

1. Connect SLD and FE for reducing noise interference if necessary.

*

2. For units at both ends of communication line, “DA” and “DB” must be connected with a terminator,

     however, for the unit, it is possible to set it by turning Terminator SW ON instead.

*

1

*

2

 WIRING CONNECTION WITH SLAVE DEVICES

The Unit

 

TENSION CLAMP TERMINAL BLOCK

Applicable wire size

: 0.2 – 1.5 mm

2

Stripped length

: 10mm

Recommended solderless terminal

• AI0,25-10YE  0.25 mm

2

 (Phoenix Contact)

• AI0,34-10TQ  0.34 mm

2

 (Phoenix Contact)

• AI0,5-10WH  0.5 mm

2

 (Phoenix Contact)

• AI0,75-10GY  0.75 mm

2

 (Phoenix Contact)

MODBUS FUNCTION CODES & SUPPORTED CODES

 

DATA AND CONTROL FUNCTIONS

CODE

NAME

01

Read Coil Status

Digital output from the slave (read/write)

02

Read Input Status

Status of digital inputs to the slave (read only)

03

Read Holding Registers

General purpose register within the slave (read/write)

04

Read Input Registers

Collected data from the field by the slave (read only)

05

Force Single Coil

Digital output from the slave (read/write)

06

Preset Single Registers

General purpose register within the slave (read/write)

15

Force Multiple Coils

Digital output from the slave (read/write)

16

Preset Multiple Registers

General purpose register within the slave (read/write)

 

EXCEPTION CODES

CODE

NAME

01

Illegal Function

Function code is not allowable for the slave.

02

Illegal Data Address

Address is not available within the slave.

03

Illegal Data Value

Data is not valid for the function.

04

Slave Device Failure

05

Acknowledge

06

Slave Device Busy

07

Negative Acknowledge

Summary of Contents for PATLABOR IT60SW6F

Page 1: ...ected to continuous vibration Do not subject the unit to physical impact Environmental temperature must be within 10 to 55 C 14 to 131 F with relative humidity within 10 to 90 RH in order to ensure ad...

Page 2: ...designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy a...

Page 3: ...with 0 5 Hz in establishing wire less link Off when wireless link stops working 920Run Green On when wireless communication with child device is in normal status Off at a wireless communication error...

Page 4: ...er of devices in a network Child fixed 1 to 30 devices Child fixed 31 to 60 devices Child fixed 61 to 100 devices Child fixed child moving Child fixed 1 to 30 devices Set network quality Standard reco...

Page 5: ...elow EXTERNAL DIMENSIONS unit mm A 192 224 256 288 320 352 Control Panel Cover Antenna 60 Approx 1500 Lead wires R165 1 Consult M System for other bolt length 0 1 2 3 4 5 Lamp Layers 60 1 5dia A 4 85...

Page 6: ...Configurator 1 Example of 5 layers in order red yellow green blue and white Lamp and wire color are the same 2 When selecting the same color for more than one layer cable colors comply with ordering...

Page 7: ...mm2 Phoenix Contact AI0 75 10GY 0 75 mm2 Phoenix Contact MODBUS FUNCTION CODES SUPPORTED CODES DATA AND CONTROL FUNCTIONS CODE NAME 01 Read Coil Status Digital output from the slave read write 02 Read...

Page 8: ...On Output 2 Lamp 3 0 Off 1 On Input 2 Lamp 3 0 Off 1 On Output 3 Lamp 4 0 Off 1 On Input 3 Lamp 4 0 Off 1 On Output 4 Lamp 5 0 Off 1 On Input 4 Lamp 5 0 Off 1 On Output 5 Buzzer 0 Off 1 Continuous Inp...

Reviews: