COMPONENT IDENTIFICATION

5

4

3

2

2

1

0

9

8

7

6

5

4

3

1

0

9

8

7

6

5

4

3

2

1

0

9

8

7

6

Mode

Power

Run

SD 920Link

RD

920ERR

920Run

Lamp 2

Lamp 3

Lamp 4

Lamp 5

Lamp 1

Status Indicator LED

Connector for 

Maintenance/Configurator

Buzzer Aperture

Gasket

Antenna

Operating Mode Setting

DIP SW

 FRONT VIEW (with the cover open)

 BOTTOM VIEW

ON

RS-485 
Connector

Terminator SW

FRONT

 

TERMINAL ASSIGNMENT

• Connector for Power Supply

Unit side connector: MC1,5/5-GF-3,5 (Phoenix Contact)
Cable side connector: FMC1,5/5-STF-3,5 (Phoenix Contact)

DA

DB

DG

SLD

FE

ID

FUNCTION

DA

DA

DB

DB

DG

DG

SLD

Shield

FE

Functional earth

 

STATUS INDICATOR LED

ID

COLOR

FUNCTION

Power

Green

On when power is supplied.
Blinks when the IP Reset SW is on.
Off when power is not supplied or an 
abnormality occurs in the unit.

Run

Green

On when Modbus communication is in 
normal status.
Off at Modbus communication error or 
during no Modbus communication.

SD

Green

On in sending data via RS-485 

RD

Green

On in receiving data via RS-485

920Link

Green

On when wireless link is working.
Blinks with 0.5 Hz in establishing wire-
less link.
Off when wireless link stops working.

920Run

Green

On when wireless communication with 
child device is in normal status.
Off  at a wireless communication error  
or during no communication.

920ERR

Red

On when there is no detour route.
Blinks at network authentication 
failure.
Off in normal status.

 

OPERATING MODE

(*) Factory setting

• Lamp Blinking Frequency: Mode-1

Mode-1

LAMP BLINKING FREQUENCY

OFF

Approx. 2 Hz (*)

ON

Approx. 10 Hz

• Buzzer Intermittent Frequency: Mode-2

Mode-2

BUZZER INTERMITTENT FREQUENCY

OFF

Approx. 2 Hz (*)

ON

Approx. 10 Hz

• Buzzer Volume: Mode-3, Mode-4

Mode-3

Mode-4

BUZZER VOLUME

OFF

OFF

Quiet (*)

OFF

ON

Middle

ON

OFF

Loud

ON

ON

Maximum

• Output at the Loss of Communication: Mode-6

Mode-6

OUTPUT AT THE LOSS OF COMMUNICATION

OFF

Reset the output (turned off) (*)

ON

Hold the output (maintains the last data 
received normally)

Available for Modbus communication.

• Output Logic Reverse: Mode-7

Mode-7

OUTPUT LOGIC REVERSE

OFF

Non-inverted (*)

ON

Inverted

Available for discrete input. 
Not available with blink (BLINK) or intermittence (BUZZ-
ER2), be sure to turn it off.

• Input Select: Mode-8

Mode-8

INPUT SELECT

OFF

Modbus/TCP (*)

ON

Discrete input

Selects the input signal of lamp and buzzer control.
Note: Be sure to set unused Mode-5 to OFF.

 

TERMINATOR

To enable the terminator, turn ON the terminator SW.  To 
disable the terminator, turn OFF the terminator SW.
(Factory set to OFF)

Summary of Contents for PATLABOR IT60SW6F

Page 1: ...ected to continuous vibration Do not subject the unit to physical impact Environmental temperature must be within 10 to 55 C 14 to 131 F with relative humidity within 10 to 90 RH in order to ensure ad...

Page 2: ...designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy a...

Page 3: ...with 0 5 Hz in establishing wire less link Off when wireless link stops working 920Run Green On when wireless communication with child device is in normal status Off at a wireless communication error...

Page 4: ...er of devices in a network Child fixed 1 to 30 devices Child fixed 31 to 60 devices Child fixed 61 to 100 devices Child fixed child moving Child fixed 1 to 30 devices Set network quality Standard reco...

Page 5: ...elow EXTERNAL DIMENSIONS unit mm A 192 224 256 288 320 352 Control Panel Cover Antenna 60 Approx 1500 Lead wires R165 1 Consult M System for other bolt length 0 1 2 3 4 5 Lamp Layers 60 1 5dia A 4 85...

Page 6: ...Configurator 1 Example of 5 layers in order red yellow green blue and white Lamp and wire color are the same 2 When selecting the same color for more than one layer cable colors comply with ordering...

Page 7: ...mm2 Phoenix Contact AI0 75 10GY 0 75 mm2 Phoenix Contact MODBUS FUNCTION CODES SUPPORTED CODES DATA AND CONTROL FUNCTIONS CODE NAME 01 Read Coil Status Digital output from the slave read write 02 Read...

Page 8: ...On Output 2 Lamp 3 0 Off 1 On Input 2 Lamp 3 0 Off 1 On Output 3 Lamp 4 0 Off 1 On Input 3 Lamp 4 0 Off 1 On Output 4 Lamp 5 0 Off 1 On Input 4 Lamp 5 0 Off 1 On Output 5 Buzzer 0 Off 1 Continuous Inp...

Reviews: