PROTECTIVE FUNCTIONS

 OVERLOAD (LOCK) PROTECTION

The  MRP  is  equipped  with  a  protection  circuit  against 

overload cause by for example valve catching an alien sub-
stance.

When  an  overload  is  detected,  the  MRP  stops  supplying 
power to the motor and the status LED flashes in 0.5 sec. 

intervals.
The protection is reset automatically with applying oppo-
site-direction input signal or turning power off and restart-
ing.

A foreign object caught in the valve, inappropriate adjust

-

ments, ground screw of the valve tightened too much, etc. 
are some of the causes of overload.  Check these parts and 
remove the cause of trouble for ensuring proper life of the 
actuator.

 FUSE

A fuse is equipped for protection against overload current.

When you turn the power supply on, check that the power 
LED is on.  If it is off, check that the fuse is melted.  Replace 

it with a new one.
If the new fuse is melted again soon after it has been re-

placed, there may be problems with the control PCB or the 

motor.  Contact M-System or sales representative.

 RE-STARTING TIMER

The MRP is equipped with a timer circuit which gives an 
interval  period  (0  –  10  sec.)  between  stop-restart  actions 

to prevent the motor and other internal components from 
overheating.
It is recommended to set a long restarting time when the 
ambient temperature and/or the temperature of flow mate-
rial is high.

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Summary of Contents for MRP4

Page 1: ...t A 4 20 mA DC Input resistance 250 Z Specify current See INPUT SPECIFICATIONS Voltage 6 1 5 V DC Input resistance approx 1 M 0 Specify voltage See INPUT SPECIFICATIONS 6 CE MARKING C With 0 Without 7...

Page 2: ...n frequency 60 cycles min Full closed overload signal Relay contact Full closed signal trips at approx 2 of span Rating 250 V AC 1 A cos 1 30 V DC 1 A resistive load INSTALLATION Power Consumption AC...

Page 3: ...ic limiters in order to prevent mechanical locks when the input goes below 0 or above 100 Limiters are set at approx 0 5 for the full closed side approx 100 5 for the full open side Full open closed s...

Page 4: ...3 2 4 6 5 7 8 11 9 10 With Both Full open closed Signal and Forced Open Close Signal COM2 COM1 COM3 POWER black 1 U V white 2 red 3 INPUT COM1 green 4 POSITION OUTPUT 1 5V DC yellow 5 blue 6 gray 7 b...

Page 5: ...4 23 91 42 1 65 43 1 69 35 1 38 60 2 36 110 4 33 150 5 91 98 3 86 90 3 54 130 5 12 2 08 127 5 167 6 57 17 67 10 0 043 sq 0 46 1 81 dia 4 M5 10 39 deep 2 G 1 2 CONDUIT YOKE SURFACE 36 0 1 dia 0 12 47 d...

Page 6: ...CW CW RESTART TIMER DEADBAND ADJ MODE SELECTOR Motor Control Logic Motor Driver Hi Lo Limiter Input Circuit Position Output Switching Regulator POWER Power Circuit CCW CW FORCED OPEN CLOSE SIGNAL POWE...

Page 7: ...ters 6 inches above the cover OUTDOOR USE When installing the MRP outdoor or where it is exposed to rain or water drops be sure to fasten the cable connector tightly and leave a slack of the cable Do...

Page 8: ...life of the actuator FUSE A fuse is equipped for protection against overload current When you turn the power supply on check that the power LED is on If it is off check that the fuse is melted Replace...

Page 9: ...rse Actions Operation at Abnormally Low Input Power Indicator green with power supplied Input Indicator green with input applied Status Indicator red blinks in 2 sec intervals blinks in 0 5 sec interv...

Page 10: ...L MIN SPAN MAX SPAN MRP4 1 MRP5 1 45 90 MRP6 1 MRP4 2 90 180 MRP6 2 Standard Zero Position M i n i m u m s p a n M a x i m u m s p a n M a x i m u m O p e r a t i o n R a n g e 5 d e g 5 d e g Adjusta...

Page 11: ...nal COM2 COM1 COM2 POWER black 1 U V white 2 red 3 INPUT COM1 green 4 POSITION OUTPUT 1 5V DC yellow 5 blue 6 gray 7 brown 8 FULL OPEN or FULL CLOSED SIGNAL output stem turned CCW output stem turned C...

Page 12: ...The following explanation applies to reverse action For di rect action read the value in the brackets Remark Applying an over torque to the adjustments may destroy stoppers or other sections of them U...

Page 13: ...nd Check input signal Narrow the deadband ON Flash 0 5 sec Actuator mechanism is damaged Repair Overload cause by a foreign object caught in the valve Check the valve Control PCB damaged Repair or rep...

Reviews: