background image

M2VS

P. 2 / 2

EM-508 Rev.9

TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the con-
nection diagram on the side of the unit.
When an input resistor is provided with the module, attach 
it together with input wiring to the input screw terminals.

CHECKING

1)  Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2)  Power input voltage:  Check voltage across the terminal 

13 – 14 with a multimeter.

3)  Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

4)  Output:    Check  that  the  load  resistance  meets  the  de-

scribed specifications.

ADJUSTMENT PROCEDURE

This  unit  is  calibrated  at  the  factory  to  meet  the  ordered 
specifications,  therefore  you  usually  do  not  need  any  cali-
bration.
For matching the signal to a receiving instrument or in case 
of regular calibration, adjust the output as explained in the 
following.

 HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.
1)  ZERO:  Apply 0% input and adjust output to 0%.
2)  SPAN:  Apply 100% input and adjust output to 100%.
3)  Check ZERO adjustment again with 0% input.
4)  When  ZERO  value  is  changed,  repeat  the  above  proce-

dure 1) – 3).

MAINTENANCE

Regular calibration procedure is explained below:

 CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%,  75%  and  100%  input  signal.    Check  that  the  output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of 
tolerance,  recalibrate  the  unit  according  to  the “ADJUST-
MENT PROCEDURE” explained earlier.

1

4

+

*

*

Input shunt resistor attached for current input.

INPUT

R

+

OUTPUT

9

12

U(+)

V(–)

POWER

13

14

EXTERNAL DIMENSIONS

  unit: mm (inch)

5

9

21.5 (.85)

70.5 (2.78)

84 (3.31)

10 (.39)

15 (.59)

6 (.23)

59 (2.32)

DIN RAIL
35mm wide

[4 (.16)]

8–M3

SCREW

72 (2.83)

23 (.91)

2–4.2x5

(.17x.20)

MTG HOLE

6 (.24) deep

114 (4.49)

• When mounting, no extra space is needed between units.

4

8

12

14 13

1

4 (.16)

 TERMINAL ASSIGNMENTS

5

8

9

12

14 13

INPUT RESISTOR

(model: REM2)

19

 (.

75

)

Input shunt resistor attached
for current input.

1

4

M-SYSTEM WARRANTY

M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such 
product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System’s sole liability, and purchaser’s exclusive 
remedies, under this warranty are, at M-System’s option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this 
warranty.  To submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original 
sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED 
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.  M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR 
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Summary of Contents for Mini-M Series

Page 1: ... Input resistance 1 MΩ min 5 0 5 V DC Input resistance 1 MΩ min 6 1 5 V DC Input resistance 1 MΩ min 4W 10 10 V DC Input resistance 1 MΩ min 5W 5 5 V DC Input resistance 1 MΩ min 0 Specify voltage See INPUT SPECIFICATIONS 2 OUTPUT Current A 4 20 mA DC Load resistance 750 Ω max B 2 10 mA DC Load resistance 1500 Ω max C 1 5 mA DC Load resistance 3000 Ω max D 0 20 mA DC Load resistance 750 Ω max E 0 ...

Page 2: ...imum span 1 mA Offset Max 1 5 times span Load resistance Output drive 15 V max DC Voltage 10 15 V DC Minimum span 5 mV Maximum span 22 V Offset Max 1 5 times span Load resistance Output drive 1 mA max at 0 5 V INSTALLATION Power Consumption AC Approx 3 VA at 100 V Approx 4 VA at 200 V Approx 5 VA at 264 V DC Approx 3 W Operating temperature 5 to 55 C 23 to 131 F Operating humidity 30 to 90 RH non ...

Page 3: ...9 12 14 13 INPUT RESISTOR model REM2 19 75 Input shunt resistor attached for current input 1 4 SCHEMATIC CIRCUITRY CONNECTION DIAGRAM Isolation Base Socket S Z 1 Low Drift Amplifier Output Driver OUTPUT 4 5 8 9 12 U V POWER 13 14 Input shunt resistor attached for current input INPUT R Specifications are subject to change without notice Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0...

Page 4: ...OWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 100 240V and 85 264V AC rating 85 264V 90 264V for UL 47 66 Hz approx 3 5VA 24V DC rating 24V 10 approx 3W 11 27V DC rating 11 27V approx 3W 110V DC rating 85 150V 110V 10 for UL approx 3W GENERAL PRECAUTIONS Before you remove the unit from its base socket or...

Page 5: ...xplained earlier 1 4 Input shunt resistor attached for current input INPUT R OUTPUT 9 12 U V POWER 13 14 EXTERNAL DIMENSIONS unit mm inch 5 9 21 5 85 70 5 2 78 84 3 31 10 39 15 59 6 23 59 2 32 DIN RAIL 35mm wide 4 16 8 M3 SCREW 72 2 83 23 91 2 4 2x5 17x 20 MTG HOLE 6 24 deep 114 4 49 When mounting no extra space is needed between units 4 8 12 14 13 1 4 16 TERMINAL ASSIGNMENTS 5 8 9 12 14 13 INPUT ...

Reviews: