I/O RANGE SELECTOR
PC Configurator Software is used to change input and out-
put specifications.
For the input codes S2 and Z1, the input range selector
switch must be positioned to the H side. Check the switch
position before you attempt to change the input type and
calibration range.
■
INPUT RANGE SELECTOR
INPUT TYPE
SWITCH POSITION
S2: -10 to +10V DC
H
Z1: 0 to 50mA DC
H
All others
L
UP/DOWN Switches
Configurator Jack
■
FRONT VIEW (with cover open)
Status Indicator LED
Zero/Span Selector
Top: SPAN
Middle: OFF
Bottom: ZERO
Address Setting Rotary SW
Modbus Term. Resistor
: OFF
: ON
The front cover cannot be opened to 180 deg.
when flush with neighboring units.
■
RIGHT SIDE VIEW
Input Range Selector
Position H
Position L
: code S2, Z1
: other
STATUS INDICATOR LED
The M2XUM is provided with a status indicator LED which
blinks in different patterns indicating various status of its
CPU.
When it is functioning within normal parameters, the LED
blinks in a regular pattern of ON and OFF.
When the unit is in an abnormality, it blinks in particular
patterns repeating approximately in 1.3 seconds.
The following figure indicates typical patterns. A white
circle means that the light is OFF for 80 millisec., while a
black one means ON for 80 millisec.
Running mode
Burnout
MAINTENANCE
Regular calibration procedure is explained below:
■
CALIBRATION
Warm up the unit for at least 20 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out
of tolerance, recalibrate the unit according to the “HARD-
WARE ADJUSTMENT” explained earlier.
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.