HOW TO RESET
After you calibrated manually with these switches, you
can reset them to its ex-factory state by pressing both UP/
DOWN switches at once.
■
ADJUSTMENT PROCEDURE
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 20 minutes.
1) ZERO: Apply 0% input. Slide the Zero/Span Selector to
the bottom position. Press UP or DOWN switch and ad-
just output to 0%.
2) SPAN: Apply 100% input. Slide the Zero/Span Selector
to the top position. Press UP or DOWN switch and adjust
output to 100%.
3) Check ZERO adjustment again with 0% input.
4) The ZERO and SPAN adjustments are processed in a dig-
ital processor, and therefore they do not interact. Howev-
er, if ZERO value is changed, repeat the above procedure
1) – 3).
I/O RANGE MODIFICATION
Configurator Software is used to change T/C type and tem-
perature range.
Output ranges can be changed over the described range of
the selected suffix code with the Configurator Software.
For changing out of this range, set the Output Range Selec-
tors before software adjustment.
UP/DOWN Switches
The front cover cannot be turned open by 180 deg.
when there is no extra space between units.
Configurator Jack
■
FRONT VIEW (with cover open)
Status Indicator LED
Zero/Span Selector
Top: SPAN
Middle: OFF
Bottom: ZERO
■
LEFT SIDE VIEW
(with cover removed)
Output Range Selectors
[e.g.]
Output code V1
O
N
2
1
3
4
5
6
7
8
O N
2
1
3 4
SW2
ATT
SW3
SW6
SW4
SW7
I
V
I
V
•
Output range selectors
SW2
SW3
1
2
3
4
V1
OFF
OFF
ON
ON
Not ATT
V2
OFF
OFF
ON
ON
Not ATT
Z1
ON
ON
OFF
OFF
Not ATT
SW4
1
2
3
4
5
6
7
8
V1
ON
ON OFF ON
ON
*
ON OFF
V2
ON OFF ON OFF ON
*
ON OFF
Z1
OFF OFF ON OFF OFF OFF OFF OFF
SW6
SW7
V
I
V
I
V1
ON
OFF
ON
OFF
V2
ON
OFF
ON
OFF
Z1
OFF
ON
OFF
ON
* ON/OFF position is irrelevant.
STATUS INDICATOR LED
The M2XT2 is provided with a status indicator LED which
blinks in different patterns indicating various status of its
CPU.
When it is functioning within normal parameters, the LED
blinks in a regular pattern of ON and OFF.
When the unit is in an abnormality, it blinks in particular
patterns repeating approximately in 1.3 seconds.
The following figure indicates typical patterns. A white
circle means that the light is OFF for 80 millisec., while a
black one means ON for 80 millisec.
Running mode
Undefined functions
Program mode
Burnout
MAINTENANCE
Regular calibration procedure is explained below:
■
CALIBRATION
Warm up the unit for at least 20 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out
of tolerance, recalibrate the unit according to the “ZERO/
SPAN ADJUSTMENTS” explained earlier.
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.