MAINTENANCE
Even lightning in remote locations could induce surges
without our knowledge. Regular checking of the surge pro-
tector is important to find degradations in early stage, be-
fore and after the storm seasons, and whenever you experi-
ence a strong lightning storm.
DO NOT attempt checking or replacing the surge protector
during a thunder storm for safety.
Checking procedure is as explained below:
■
CHECK EXTERIOR
If discoloration or deformation is observed, replace with a
new one immediately.
■
CHECK MONITOR LED
Green LED turns on during normal operation, indicating
the surge protector is functioning properly. Turning off
means that the protector is in failure. Replace with a new
one immediately.
When the voltage between L+ and L- is low, the monitor
LED may be dark. In that case, check the LED with a in-
sulation tester (+150 to +600 V DC). When the polarity is
opposite, change it.