MAINTENANCE

Even lightning in remote locations could induce surges 
without our knowledge.  Regular checking of the surge pro-
tector is important to find degradations in early stage, be-
fore and after the storm seasons, and whenever you experi-
ence a strong lightning storm.
DO NOT attempt checking or replacing the surge protector 
during a thunder storm for safety.
Checking procedure is as explained below:

 

CHECK EXTERIOR

If discoloration or deformation is observed, replace with a 
new one immediately.

 

CHECK MONITOR LED

Green LED turns on during normal operation, indicating 
the surge protector is functioning properly.  Turning off 
means that the protector is in failure.  Replace with a new 
one immediately.
When the voltage between L+ and L- is low, the monitor 
LED may be dark.  In that case, check the LED with a in-
sulation tester (+150 to +600 V DC).  When the polarity is 
opposite, change it.