WIRING

 

LEADWIRES

Conductor cross-section area: 5.5 mm

2

 minimum for both 

the power and the earth lines.  However, a local industrial 
standard requirement for wiring should take precedence.

 

SOLDERLESS TERMINAL

Applicable ring tongue terminal without insulation sleeve 
is as indicated below.  Spade tongue terminal must conform 
with the ring type size.
In order to ensure IP20 protection (IEC 60529) with a sol-
derless terminal, cover the terminal with a insulation cap  
to prevent direct touching by a hand.

F

d : M5 use
B ≤ 13.0 mm
F ≥ 7.0 mm
(F ≥ 8.2 mm for sharing terminals)
T ≤ 1.8 mm

• Applicable Solderless Terminal Size

diameter d

B

T

 

TORQUE

Tighten the screw terminals securely.  Maximum allowable 
torque is of 2.5 N·m.

 

WIRE LENGTH

Keep the wire length to the minimum for both the power 
source side and the earth side.  The wire length between the 
branch point and the earth should ideally be less than 0.5 
meters.  Extra long wires should not be bundled in coils, but 
be cut to the minimum required length.

EARTHING

 

COMMON EARTHING WITH CROSS-OVER WIRE

Basically a common earthing with cross-wiring between 
the MATP and the protected device is recommended for ad-
equate protection.  Earthing resistance should be less than 
100 ohms.  If the protected device has no earth terminal, 
earth only the MATP.
The earthing point should be close to the MATP side as 
shown below.

Cross-wiring

Protected 

Device

G

+

-

L+

L-

SPD

ALARM OUTPUT

Optional breack-contact relay output is available to alert 
when the thermal breaker has separated the discharge ele-
ment from the power supply circuit.
If the alarm output should be transmitted remotely via out-
door cables, a surge protector for signal line is required.
Choose a circuit breaker with an alarm output.  Configure a 
logical addition sequence so that the alarm trips when both 
or either of the MATP or the breaker alarm trips.

 

RELAY SPECIFICATIONS

Alarm output:  The breack-contact relay trips when the ther-

mal breaker operates.

Rated load:   250V AC @50mA (resistive load)
     

 

 

24V DC @50mA (resistive load)

 

CONNECTION

Terminal:  Tension clamp
Applicable wire size: 0.13 to 1.5 mm

2

Stripped length: 8 mm

CHECKING

 

WIRING

• Make sure that wiring is done as instructed in the con-

nection diagram.

• Make sure that the earth terminal (G) is connected to the 

metallic housing of protected equipment.

• Make sure that the earth terminal (G) is earthed to earth.