I/O RANGE MODIFICATION

Configurator Software is used to change input ranges over 
the described range of the selected suffix code.  For chang-
ing out of this range, set the Input Range Selectors before 
software adjustment.
For changing output ranges, set the Output Range Selector 
and then select by Configurator Software.

 

SIDE VIEW

Input Range Selector

Output Range Selector

V

V

L

I

I

H

I

I

H

V

L

V

Input Range Selector

INPUT RANGE

TOP SW

BOTTOM SW

Z1: 0 – 50 mA DC

I

L

S1: -1 – +1 V DC

V

L

S2: -10 – +10 V DC

V

H

Output Range Selector

OUTPUT RANGE

SW POSITION

V2Z1: -10 – +10 V / 0 – 20 mA DC

I

V2V2: -10 – +10 V / -10 – +10 V DC

V

STATUS INDICATOR LED

The unit is provided with a status indicator LED which 
blinks in different patterns indicating various status of its 
CPU.  When it is functioning within normal parameters, the  
LED blinks in a regular pattern of ON and OFF.
The following figure indicates typical patterns.

LED PATTERNS

STATUS

Normal

Programming Mode
Out. 1 Calibration Mode
Out. 2 Calibration Mode

200 ms

ON

OFF

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%, 75% and 100% input signal.  Check that the output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of 
tolerance, recalibrate the unit according to the “CALIBRA-
TION” explained earlier.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.

Summary of Contents for M8XV2

Page 1: ...firm its operational range as indicated below 24V DC rating 24V 10 approx 50mA 70mA for current output GENERAL PRECAUTIONS Before you remove the unit or mount it turn off the power supply and input signal for safety ENVIRONMENT Indoor use When heavy dust or metal particles are present in the air install the unit inside proper housing with sufficient ventilation Do not install the unit where it is ...

Page 2: ...ase OUTPUT 1 6 7 8 9 10 11 OUTPUT 2 1 2 A B POWER INPUT CONFIGURATOR JACK CHECKING 1 Terminal wiring Check that all cables are correctly con nected according to the connection diagram 2 DIP switches Check the input range selector and output range selector setting 3 Power input Check the power input voltage 4 Input Check that the input signal is within 0 100 of the full scale 5 Output Check that th...

Page 3: ...figurator Jack DOWN Switch BOTTOM VIEW Zero Span Selector S Z OFF Z S Zero Span Selector MODE SW POSITION SPAN S OFF ZERO Z HOW TO CALIBRATE THE ZERO SPAN Use a signal source and measuring instruments of sufficient accuracy level Turn the power supply on and warm up for more than 10 minutes The output 1 and output 2 adjustments are linked except for 2 and 6 1 Apply 0 input 2 Select the Output 1 Ze...

Page 4: ...STATUS INDICATOR LED The unit is provided with a status indicator LED which blinks in different patterns indicating various status of its CPU When it is functioning within normal parameters the LED blinks in a regular pattern of ON and OFF The following figure indicates typical patterns LED PATTERNS STATUS Normal Programming Mode Out 1 Calibration Mode Out 2 Calibration Mode 200 ms ON OFF MAINTENA...

Reviews: