EM-7919  Rev.4  P. 3 / 3

 

CONNECTION DIAGRAM

1

3

2

5

6

+

+

+

+

OUTPUT

POWER

INPUT

SENSOR EXCITATION

CONNECTOR

POWER

7

8

 Mechanical Contact or Open Collector

Input Connection Examples 

 Voltage Pulse

+12V

 Open Collector

Output Connection Examples 

+

5

6

+

 Voltage Pulse

+

5

6

+

+

+


PWR

+

+


PWR

+

1

2

+ 3

+

1

2

+ 3

 2-Wire Current Pulse

 External DC Supply

+

2-WIRE

PICK-UP

1

2

3

+

2-WIRE

PICK-UP

1

2

3

DC SUPPLY

+

+

 Built-in Excitation

200 Ω

+12V

5 kΩ

+12V

200 Ω

+12V

WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.5 N·m

 

SOLDERLESS TERMINAL  unit: mm (inch)

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.
Solderless terminals with insulation sleeve do not fit.
Applicable wire size: 0.2 – 2.5 mm

2

3.2 (.13) dia.

4 min.

(.16)

5.8 max.

(.23)

5.5 max.
 (.22) 

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage across the terminal 

7 – 8 with a multimeter.

3) Input: Check that the input frequency is 30 Hz or less 

for relay contact, 100 kHz or less for other types of input.  

Check also that input pulse is 10 msec. or wider for relay 

contact, 5 µsec. or wider for other types of input.

4) Output: Check that the load resistance meets the de-

scribed specifications as shown below. 

OUTPUT

LOAD REQUIREMENTS

Open collector

50 V DC @ 100 mA max.

Voltage pulse

1.0 kΩ min. for 5 V 
2.4 kΩ min. for 12 V 
4.8 kΩ min. for 24 V

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.