background image

MODEL: M6DXAT

  Trip action: High
  Relay coil at alarm: Energized
  Power ON delay time: 5 sec.
  Alarm ON delay time: 0 sec.
  Hysteresis (deadband) : 1.0 %
  Burnout: Upscale

INPUT SPECIFICATIONS

Input resistance: 1 MΩ min.
Burnout sensing: ≤ 0.1 μA
Temperature range: See Table 1.
If not specified, the input range is shown below.
1 PR: 0 – 1600°C
2 K: 0 – 1000°C
3 E: 0 – 500°C
4 J: 0 – 500°C
5 T: 0 – 300°C
6 B: 500 – 1600°C
7 R: 500 – 1600°C
8 S: 0 – 1600°C
N N: 0 – 1000°C

OUTPUT SPECIFICATIONS

• RELAY OUTPUT
Relay rating:
250 V AC @2 A (cos ø = 1)
30 V DC @2 A (resistive load)
Maximum switching voltage: 250 V AC or 125 V DC
Maximum switching power: 500 VA or 60 W
Minimum load: 5 V DC @100 mA
Mechanical life: 5 × 10

6

 cycles (rate 180/min.)

0

50

100

Input
(%)

Setpoint

Output

(3–4)ON

(3–2)ON

• Setting Example
     Hi alarm (coil energized at alarm) or
     Lo alarm (coil de-energized at alarm)

Alarm Trip Operation  

Terminal No. in parentheses

Trip operation in power failure

: Terminals 3 – 4 turn ON.

INSTALLATION

Power consumption: Approx. 0.5 W
Operating temperature: -20 to +55°C (-4 to +131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Installation Base (model: M6DBS) or DIN rail
Weight: 65 g (2.3 oz)

PERFORMANCE in percentage of span

Setpoint accuracy (trip point accuracy):
Accuracy in Table 1 + Cold junction compensation error
Cold junction compensation error:
±3°C at 25 ±10°C
±5.4°F at 77 ±18°F
Temp. coefficient: ±0.01 %/°C (±0.006 %/°F) of max. span
Response time: ≤ 0.5 sec. (0 – 100 % at 90 % setpoint)
Burnout response time: ≤ 1 sec.
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute  (input to output
to power to ground)

CALCULATION EXAMPLES OF SETPOINT ACCURACY

[Example] K thermocouple, 0 – 1000°C
Absolute value accuracy (Table 1): 0.25°C
CJC error (3°C) added: 3.25°C
Setpoint accuracy = 3.25°C / 1000°C × 100 = 0.33 %

Table 1.

 

 

THERMOCOUPLE

 

MIN. 

MAXIMUM 

CONFORMANCE 

ACCURACY 

MIN. 

MAXIMUM 

CONFORMANCE 

ACCURACY

 

 

 

SPAN 

RANGE 

RANGE 

SPAN 

RANGE 

RANGE 

 

(PR) 

20 

0 to  1760 

0 to  1760 

±

1.00 

36 

32 to  3200 

32 to  3200 

±

1.80

K  (CA) 

20 

-270 to +1370  -150 to +1370 

±

0.25 

36 

-454 to +2498  -238 to +2498 

±

0.45

E  (CRC) 

20 

-270 to +1000  -170 to +1000 

±

0.20 

36 

-454 to +1832  -274 to +1832 

±

0.36

J  (IC) 

20 

-210 to +1200  -180 to +1200 

±

0.25 

36 

-346 to +2192  -292 to +2192 

±

0.45

T  (CC) 

20 

-270 to  +400  -170 to  +400 

±

0.25 

36 

-454 to  +752  -274 to  +752 

±

0.45

B  (RH) 

20 

100 to  1820 

400 to  1760 

±

0.75 

36 

212 to  3308 

752 to  3200 

±

1.35

R   

20 

-50 to +1760 

200 to  1760 

±

0.50 

36 

-58 to +3200 

392 to  3200 

±

0.90

S   

20 

-50 to +1760 

0 to  1760 

±

0.50 

36 

-58 to +3200 

32 to  3200 

±

0.90

N   

20 

-270 to +1300  -130 to +1300 

±

0.30 

36 

-454 to +2372  -202 to +2372 

±

0.54

 

 

 

 

(PR) 

K  (CA) 

E  (CRC) 

J  (IC) 

T  (CC) 

B  (RH) 

R   

S   

N   

THERMOCOUPLE

STANDARDS & APPROVALS

CE conformity:
  EMC Directive (2004/108/EC)
  EN 61000-6-4 (EMI)
  EN 61000-6-2 (EMS)
  Low Voltage Directive (2006/95/EC)
  EN 61010-1
  Overvoltage Category II

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Summary of Contents for M6D Series

Page 1: ...types GENERAL SPECIFICATIONS Connection Input and output Euro terminal torque 0 3 N m Power input Via the Installation Base model M6DBS or Euro terminal torque 0 3 N m Applicable wire size 0 2 to 2 5...

Page 2: ...C 0 006 F of max span Response time 0 5 sec 0 100 at 90 setpoint Burnout response time 1 sec Line voltage effect 0 1 over voltage range Insulation resistance 100 M with 500 V DC Dielectric strength 20...

Page 3: ...k Power LED Alarm Monitor LED DIMENSIONS unit mm inch 94 3 70 5 9 23 DIN RAIL HOOK 102 4 02 0 5 02 8 M3 EURO TERMINAL DIN RAIL 35mm wide 5 6 7 8 1 2 3 4 When mounting no extra space is needed between...

Page 4: ...uctive Load Coil Diode Varistor or CR Circuit POWER OUTPUT Ry CONFIGURATOR JACK STATUS LED ALARM MONITOR LED Digital Computation T C comp leadwire CJC SENSOR CONNECTOR POWER POWER LED Specifications a...

Page 5: ...such that appropriate clearance and creepage distances are maintained to con form to CE requirements Failure to observe these re quirements may invalidate the CE conformance POWER INPUT RATING OPERATI...

Page 6: ...to the DIN rail REMOVING THE UNIT A Pull down the DIN rail adaptor using a minus screw driver B Pull out the lower part of the unit C Remove the upper part from the DIN rail DIN Rail A B DIN Rail Adap...

Page 7: ...L DIN RAIL 35mm wide 5 6 7 8 1 2 3 4 When mounting no extra space is needed between units WIRE INSERTION ANGLE approx 7 SCREWDRIVER INSERTION ANGLE approx 40 2 4 3 NC NO COM 5 6 OUTPUT POWER CONFIGURA...

Page 8: ...xplained below CALIBRATION Warm up the unit for at least 10 minutes H Setpoint Increase the input signal from a value lower than the set point and check that the relay trips at the H setpoint within t...