CONNECTION DIAGRAM

+

OUTPUT

5

6

+

INPUT

1

2

+

OUTPUT

7

8

+

INPUT

3

4

Channel 1

Channel 2

WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.5 N·m

 

SOLDERLESS TERMINAL  unit: mm (inch)

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.
Solderless terminals with insulation sleeve do not fit.
Applicable wire size: 0.2 – 2.5 mm

2

3.2 (.13) dia.

4 min.

(.16)

5.8 max.

(.23)

5.5 max.
 (.22) 

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Input:  Check current with an ammeter.  Be sure that the 

connected transmitter allows the unit’s load value [250 Ω 

+ output load resistance].

3) Output:  Check that output load is within the permissible 

limit of 600 Ω.

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory to meet the ordered 
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case 
of regular calibration, adjust the output as explained in the 
following.

 

HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the input signal on and warm up for 
more than 10 minutes.

1) SPAN:  Apply 100% input and adjust output to 100%.

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 25%, 50%, 
75% and 100% input signal.  Check that the output signal 
for the respective input signal remains within accuracy de-
scribed in the data sheet.  When the output is out of toler-
ance, recalibrate the unit according to the “ADJUSTMENT 
PROCEDURE” explained earlier.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.