background image

MODEL: M5VS

SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)

/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

ADJUSTMENT

/V01: Multi-turn fine adjustment
/VN: Sealed adjustment holes

GENERAL SPECIFICATIONS

Construction: Terminal block
Connection: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Zero adjustment: -2 to +2 % (front)
(±1 % with the input suffix codes 4W and 5W selected)
Span adjustment: 98 to 102 % (front)
(99 to 101 % with the input suffix codes 4W and 5W
selected.)
Power LED: Green light turns on when the power is supplied.

INPUT SPECIFICATIONS

■ DC Current: Input resistor incorporated
Specify input resistance value for code Z.
(R ≤ 0.125 W ÷ [F.S. Current]

2

)

■ DC Voltage
Input resistance: 1 MΩ min. (10 kΩ min. at power loss)
Input code 0 (Not CE)
   Voltage range: -300 – +300 V DC
   Minimum span: 100 mV
   Offset: Max. 1.5 times span
Input code 01 (CE)
   Voltage range: -70 – +70 V DC
   Minimum span: 100 mV
   Offset: Max. 1.5 times span
Input code 02 (Not CE)
   Voltage range: 0 – 500 V DC
   Minimum span: 200 V
  

 

Offset: Max. 1.5 times span

   Input at 100%: min. 300 V

OUTPUT SPECIFICATIONS

■ DC Current: 0 – 20 mA DC
  Minimum span: 1 mA
  Offset: Max. 1.5 times span
  Load resistance: Output drive 11 V max.
■ DC Voltage
Output code 0 (CE)
 Voltage range: -10 – +10 V DC
 Minimum span: 1 V

 Offset: Max. 1.5 times span
 Load resistance: Output drive 10 mA max.; at ≥1 V
 Max. 1.25 mA output drive for negative voltage
Output code 01 (Not CE)

 

Voltage range: -1 – +1 V DC

 

Minimum span: 10 mV

 

Offset: Max. 1.5 times span

 

Load resistance: Min. 100 kΩ

 

Min. 1 MΩ for negative voltage

INSTALLATION

Power Consumption
•AC Power input:
  Approx. 2 VA at 100 V
  Approx. 3 VA at 200 V
  Approx. 3 VA at 264 V
•DC power input: Approx. 2 W
Operating temperature: -5 to +55°C (23 to 131°F)
0 to 40°C (32 to 104°F) for the input code 02
Operating humidity: 0 to 90 %RH (non-condensing)
30 to 70 %RH (non-condensing) for the input code 02
Mounting: DIN rail
Weight: 80 g (2.8 oz)

PERFORMANCE in percentage of span

Accuracy: ±0.1 %
±0.2 % for the input code 02
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
±0.02 %/°C (±0.01 %/°F) at input <1 V and output <5 mA
±0.03 %/°C (±0.017 %/°F) for the input code 02
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength (input to output to power to ground)
  DC powered: 2000 V AC @1 minute
  AC powered: 1500 V AC @1 minute

STANDARDS & APPROVALS

CE conformity:
EMC Directive (2004/108/EC)
  EMI EN 61000-6-4: 2007
  EMS EN 61000-6-2: 2005

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Summary of Contents for M5VS Series

Page 1: ...ECIFICATIONS Choose 01 for CE Power suffix code R only 02 Specify voltage See INPUT SPECIFICATIONS CE not available 2 OUTPUT Current A 4 20 mA DC Load resistance 550 Ω max D 0 20 mA DC Load resistance 550 Ω max Z Specify current See OUTPUT SPECIFICATIONS Voltage 1 0 10 mV DC Load resistance 100 kΩ min CE not available 2 0 100 mV DC Load resistance 100 kΩ min CE not available 3 0 1 V DC Load resist...

Page 2: ...mum span 1 mA Offset Max 1 5 times span Load resistance Output drive 11 V max DC Voltage Output code 0 CE Voltage range 10 10 V DC Minimum span 1 V Offset Max 1 5 times span Load resistance Output drive 10 mA max at 1 V Max 1 25 mA output drive for negative voltage Output code 01 Not CE Voltage range 1 1 V DC Minimum span 10 mV Offset Max 1 5 times span Load resistance Min 100 kΩ Min 1 MΩ for nega...

Page 3: ... 4 1 39 1 2 3 4 5 6 7 8 SCHEMATIC CIRCUITRY CONNECTION DIAGRAM Isolation S Z Low Drift Amplifier Output Driver INPUT 3 4 1 2 Input shunt resistor incorporated for current input OUTPUT 5 6 8 7 U V POWER POWER LED Specifications are subject to change without notice Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox sentronic com www sentronic com Produkte Support und...

Page 4: ...ature must be within 5 to 55 C 23 to 131 F with relative humidity within 0 to 90 RH in order to ensure adequate life span and operation WIRING Do not install cables power supply input and output close to noise sources relay drive cable high frequency line etc Do not bind these cables together with those in which noises are present Do not install them in the same duct Install lightning surge protec...

Page 5: ... units DIN RAIL 35mm wide 8 M3 5 SCREW 7 3 29 1 2 3 4 5 6 7 8 OUTPUT 5 6 7 8 INPUT 3 4 U V POWER CHECKING 1 Terminal wiring Check that all cables are correctly con nected according to the connection diagram 2 Power input voltage Check voltage across the terminal 7 8 with a multimeter 3 Input Check that the input signal is within 0 100 of the full scale 4 Output Check that the load resistance meets...

Reviews: