M5VS

P. 1 / 2

EM-2468 Rev.7

SIGNAL TRANSMITTER

MODEL

M5VS

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 PACKAGE INCLUDES:

  Signal conditioner ......................................................... (1)
  Sealing label (option /VN) .................................. (1 sheet)

 MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 POWER INPUT RATING & OPERATIONAL RANGE

• Locate the power input rating marked on the product and 

confirm its operational range as indicated below:

  85 – 264V AC rating: 85 – 264V, 47 – 66 Hz, approx. 2 – 3VA
  24V DC rating: 24V ±10%, approx. 2W

 GENERAL PRECAUTIONS

• Before you remove the unit or mount it, turn off the power 

supply and input signal for safety.

 ENVIRONMENT

• Indoor use
• When heavy dust or metal particles are present in the air, 

install the unit inside proper housing with sufficient ven-
tilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -5 to +55°C     

(23 to 131°F) with relative humidity within 0 to 90% RH 

in order to ensure adequate life span and operation.

 WIRING

• Do  not  install  cables  (power  supply,  input  and  output) 

close to noise sources (relay drive cable, high frequency 
line, etc.).

• Do  not  bind  these  cables  together  with  those  in  which 

noises are present.  Do not install them in the same duct.

• Install lightning surge protectors for those wires connect

-

ed  to  remote  locations.    For  24V  DC  power  supply  line, 

choose a surge protector with its maximum surge voltage 

40V or less between lines.  Recommended M-System mod

-

el: MDP-D24.

 AND ....

• The unit is designed to function as soon as power is sup

-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

COMPONENT IDENTIFICATION

INSTALLATION

Set the unit so that its DIN rail adapter is at the bottom.

 MOUNTING THE UNIT ON A DIN RAIL

A) Hang the upper hook at the rear side of unit on the DIN 

rail.

B) Push in the lower in keeping pressing the unit to the 

DIN rail.

 REMOVING THE UNIT

A) Push down the DIN rail adaptor using a minus screw-

driver.

B) Pull out the lower part of the unit.

C) Remove the upper part from the DIN rail.

Power LED

Terminal Cover

Zero Adj.

Span Adj.

Body

Spec. Marking

A

B

DIN Rail

A

C

B

Spring Loaded

DIN Rail Adaptor

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Summary of Contents for M5VS Series

Page 1: ...ECIFICATIONS Choose 01 for CE Power suffix code R only 02 Specify voltage See INPUT SPECIFICATIONS CE not available 2 OUTPUT Current A 4 20 mA DC Load resistance 550 Ω max D 0 20 mA DC Load resistance 550 Ω max Z Specify current See OUTPUT SPECIFICATIONS Voltage 1 0 10 mV DC Load resistance 100 kΩ min CE not available 2 0 100 mV DC Load resistance 100 kΩ min CE not available 3 0 1 V DC Load resist...

Page 2: ...mum span 1 mA Offset Max 1 5 times span Load resistance Output drive 11 V max DC Voltage Output code 0 CE Voltage range 10 10 V DC Minimum span 1 V Offset Max 1 5 times span Load resistance Output drive 10 mA max at 1 V Max 1 25 mA output drive for negative voltage Output code 01 Not CE Voltage range 1 1 V DC Minimum span 10 mV Offset Max 1 5 times span Load resistance Min 100 kΩ Min 1 MΩ for nega...

Page 3: ... 4 1 39 1 2 3 4 5 6 7 8 SCHEMATIC CIRCUITRY CONNECTION DIAGRAM Isolation S Z Low Drift Amplifier Output Driver INPUT 3 4 1 2 Input shunt resistor incorporated for current input OUTPUT 5 6 8 7 U V POWER POWER LED Specifications are subject to change without notice Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox sentronic com www sentronic com Produkte Support und...

Page 4: ...ature must be within 5 to 55 C 23 to 131 F with relative humidity within 0 to 90 RH in order to ensure adequate life span and operation WIRING Do not install cables power supply input and output close to noise sources relay drive cable high frequency line etc Do not bind these cables together with those in which noises are present Do not install them in the same duct Install lightning surge protec...

Page 5: ... units DIN RAIL 35mm wide 8 M3 5 SCREW 7 3 29 1 2 3 4 5 6 7 8 OUTPUT 5 6 7 8 INPUT 3 4 U V POWER CHECKING 1 Terminal wiring Check that all cables are correctly con nected according to the connection diagram 2 Power input voltage Check voltage across the terminal 7 8 with a multimeter 3 Input Check that the input signal is within 0 100 of the full scale 4 Output Check that the load resistance meets...

Reviews: