INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Signal conditioner ...............................................................(1)
Sensor ..................................................................................(1)
Cable (CLSA-08, -12 only) ..................................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 

POWER INPUT RATING & OPERATIONAL RANGE

• Locate the power input rating marked on the product and 

confirm its operational range as indicated below:

  85 – 264V AC rating: 85 – 264V, 47 – 66 Hz, approx. 2 – 3VA
    24V DC rating: 24V ±10%, approx. 2W

 

GENERAL PRECAUTIONS

• Before you remove the unit or mount it, turn off the power 

supply and input signal for safety.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -5 to +55°C     

(23 to 131°F) with relative humidity within 0 to 90% RH 
in order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

• Install lightning surge protectors for those wires connect-

ed to remote locations.  For 24V DC power supply line, 
choose a surge protector with its maximum surge voltage 
40V or less between lines.  Recommended M-System mod-
el: MDP-D24.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

COMPONENT IDENTIFICATION

Specifications

Power LED

Terminal Cover

Zero Adj.

Span Adj.

Body

INSTALLATION

Set the unit so that its DIN rail adapter is at the bottom.

 

MOUNTING THE UNIT ON A DIN RAIL

A) Hang the upper hook at the rear side of unit on the DIN 

rail.

B) Push in the lower in keeping pressing the unit to the DIN 

rail.

A

B

DIN Rail

 

REMOVING THE UNIT

A) Push down the DIN rail adaptor using a minus screw-

driver.

B) Pull out the lower part of the unit.
C) Remove the upper part from the DIN rail.

A

C

B

Spring Loaded

DIN Rail Adaptor

 

CLAMP-ON CURRENT SENSOR

Secure the sensor to the cable e.g. using tie wraps.
Over-voltage clamp element is incorporated for safety in 
open circuit.

CT TRANSMITTER

(clamp-on current sensor)

MODEL

M5CTC

Summary of Contents for M5CTC

Page 1: ...o physical impact Environmental temperature must be within 5 to 55 C 23 to 131 F with relative humidity within 0 to 90 RH in order to ensure adequate life span and operation WIRING Do not install cables close to noise sources relay drive cable high frequency line etc Do not bind these cables together with those in which noises are present Do not install them in the same duct Install lightning surg...

Page 2: ...pplicable cable diameter Max 10 0 Sensor leadwire AWG 22 Weight 45 g 1 6 oz L K 10 39 dia 41 1 61 23 91 27 1 05 26 1 02 150 5 91 3000 118 l k 0 100A Use Sensor model No CLSA 12 Sensor cable model No CLSA 08C 30 Applicable cable diameter Max 16 0 Sensor leadwire AWG 22 Weight 70 g 2 5 oz 16 63 dia 44 5 1 75 29 1 14 30 1 18 31 1 22 150 5 91 l k L K 3000 118 0 125A through 0 300A Use Sensor model No ...

Page 3: ...g 7 1 oz k k l l 2 M3 SCREW 55 9 2 20 35 9 1 41 8 3 33 8 3 33 75 7 2 98 24 dia 94 TERMINAL COVER detachable K L 0 225A through 0 400A Use Sensor model No CLSB 40 Applicable cable diameter Max 35 0 Weight 300 g 10 6 oz 35 dia 1 38 k k l l 2 M3 SCREW K L 73 5 2 89 35 5 1 40 8 8 35 8 8 35 93 3 66 TERMINAL COVER detachable 0 500A through 0 600A Use Sensor model No CLSB 60 Applicable cable diameter Max...

Page 4: ...e output as explained in the following HOW TO CALIBRATE THE OUTPUT SIGNAL Use a signal source and measuring instruments of sufficient accuracy level Turn the power supply on and warm up for more than 10 minutes 1 ZERO Apply 10 input and adjust output to 10 2 SPAN Apply 100 input and adjust output to 100 3 Check ZERO adjustment again with 10 input 4 When ZERO value is changed repeat the above proce...