27
M3LDY OPERATING MANUAL EM-2664-B Rev.0
10.2.2 MAXIMUM RANGE AND MINIMUM sPAN OF INPUT
The maximum range and minimum span of the input are shown in the following tables.
10.2.2.1 DC current input
MAXIMUM RANGE
MINIMUM SPAN
0 to 20 mA DC
2 mA
NOTE
The ex-factory setting is 4 – 20 mA DC unless otherwise specified.
10.2.3 MAXIMUM RANGE, MINIMUM sPAN AND DEFAULT VALUE OF OUTPUT
The maximum range, minimum span and default value of the output are shown in the following tables. The default value
means initial 0% and 100% output when the DIP switch setting is changed.
10.2.3.1 DC current output
MAXIMUM RANGE
MINIMUM SPAN
DEFAULT VALUE
0 to 20 mA DC
1 mA
4 to 20 mA DC
10.2.3.2 DC voltage output (narrow spans)
MAXIMUM RANGE
MINIMUM SPAN
DEFAULT VALUE
-2.5 to +2.5 V DC
250 mV
-1 to +1 V DC
10.2.3.3 DC voltage output (wide spans)
MAXIMUM RANGE
MINIMUM SPAN
DEFAULT VALUE
-10 to +10 V DC
1 V
1 to 5 V DC
NOTE
The ex-factory setting is 4 – 20 mA DC unless otherwise specified.