background image

M2SBS

TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the con-
nection diagram on the side of the unit.

CHECKING

1)  Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2)  Power input voltage:  Check voltage across the terminal 

13 – 14 with a multimeter.

3)  Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

4)  Output:    Check  that  the  load  resistance  meets  the  de-

scribed specifications.

ADJUSTMENT PROCEDURE

This  unit  is  calibrated  at  the  factory  to  meet  the  ordered 
specifications,  therefore  you  usually  do  not  need  any  cali-
bration.
For matching the signal to a receiving instrument or in case 
of regular calibration, adjust the output as explained in the 
following.

 HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.

1)  ZERO:   Apply  the  input  signals  which  should  lead  the 

calculated result as 0%, and adjust output to 0%.

2)  SPAN:  [K

1

 ≥ 1]  Apply the input signals which should 

lead the calculated result as 100%, and adjust output to 
100%.

  [K

1

 < 1]  Apply the input signals which should lead the 

calculated  result  as  [100 

×

  K

1

]%,  and  adjust  output  to 

[100 

×

 K

1

]%.

3)  Check ZERO adjustment again.
4)  When  ZERO  value  is  changed,  repeat  the  above  proce-

dure 1) – 3).

EQUATION

  Output = K

1

 

×

 Input 1 – K

2

 

×

 Input 2

     

(K

1

 

×

 Input 1 > K

2

 

×

 Input 2)

     

K

1

: 0.40 to 2.00 specified when ordering

     

K

2

: 0.10 to 2.00 specified when ordering

     

Input 1, Input 2: 0 to 120%

     

Forcibly limited to 0% and 120% respectively when  

     

the signal is out of range.

MAINTENANCE

Regular calibration procedure is explained below:

 CALIBRATION

Warm up the unit for at least 10 minutes.
[K

1

 ≥ 1]  Apply the input signals which should lead the cal-

culated result as 0%, 25%, 50%, 75% and 100%.  Check that 
the  output  signal  for  the  respective  input  signal  remains 
within accuracy described in the data sheet.
[K

1

 < 1]  Apply the input signals which should lead the cal-

culated result as 0%, [25 

×

 K

1

]%,  [50 

×

 K

1

]%,  [75 

×

 K

1

]% and  

[100 

×

 K

1

]%.  Check that the output signal for the respective 

input signal remains within accuracy described in the data 
sheet.
When the output is out of tolerance, recalibrate the unit ac-
cording  to  the  “ADJUSTMENT  PROCEDURE”  explained 
earlier.

EXTERNAL DIMENSIONS

  unit: mm (inch)

5

9

21.5 (.85)

70.5 (2.78)

84 (3.31)

10 (.39)

15 (.59)

6 (.23)

59 (2.32)

DIN RAIL
35mm wide

[4 (.16)]

8–M3

SCREW

72 (2.83)

23 (.91)

2–4.2x5

(.17x.20)

MTG HOLE

6 (.24) deep

114 (4.49)

• When mounting, no extra space is needed between units.

4

8

12

14 13

1

4 (.16)

1

4

+

INPUT 1

5

8

+

INPUT 2

+

OUTPUT

9

12

U(+)

V(–)

POWER

13

14

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Summary of Contents for M Series

Page 1: ...esistance 1 MΩ min 5 0 5 V DC Input resistance 1 MΩ min 6 1 5 V DC Input resistance 1 MΩ min 4W 10 10 V DC Input resistance 1 MΩ min 5W 5 5 V DC Input resistance 1 MΩ min 0 Specify voltage See INPUT SPECIFICATIONS 2 INPUT 2 Same range availability as Input 1 3 OUTPUT Current A 4 20 mA DC Load resistance 750 Ω max B 2 10 mA DC Load resistance 1500 Ω max C 1 5 mA DC Load resistance 3000 Ω max D 0 20...

Page 2: ... 1 V 1 MΩ OUTPUT SPECIFICATIONS DC Current 0 20 mA DC Minimum span 1 mA Offset Max 1 5 times span Load resistance Output drive 15 V max DC Voltage 10 12 V DC Minimum span 5 mV Offset Max 1 5 times span Load resistance Output drive 1 mA max at 0 5 V INSTALLATION Power Consumption AC Power input Approx 3 VA at 100 V Approx 4 VA at 200 V Approx 5 VA at 264 V DC Power input Approx 3 W Operating temper...

Page 3: ...16 SCHEMATIC CIRCUITRY CONNECTION DIAGRAM Isolation Base Socket S Z 1 Low Drift Amplifier Output Driver OUTPUT 4 5 8 9 Input shunt resistor incorporated for current input Low Drift Amplifier INPUT 2 INPUT 1 Digital Computation U V POWER 12 13 14 Specifications are subject to change without notice Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox sentronic com www ...

Page 4: ...ANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 100 240V AC rating 85 264V 90 264V for UL 47 66 Hz approx 3 5VA 24V DC rating 24V 10 approx 3W 11 27V DC rating 11 27V approx 3W 110V DC rating 85 150V 110V 10 for UL approx 3W GENERAL PRECAUTIONS Before you remove the unit from its base socket or mount it turn off the power supply and inp...

Page 5: ...k ZERO adjustment again 4 When ZERO value is changed repeat the above proce dure 1 3 EQUATION Output K1 Input 1 K2 Input 2 K1 Input 1 K2 Input 2 K1 0 40 to 2 00 specified when ordering K2 0 10 to 2 00 specified when ordering Input 1 Input 2 0 to 120 Forcibly limited to 0 and 120 respectively when the signal is out of range MAINTENANCE Regular calibration procedure is explained below CALIBRATION Wa...

Reviews: