M-system KS2V3 Instruction Manual Download Page 4

KS2V3

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-3603  Rev.3  P. 4 / 9

 

DEFAULT PARAMETER SETTING

Param.
Block

Name

Default setting Unit

Programmable range

Explanations of function

1*

3

ST1

100.0

Engineering unit*

6

-5 to +105 % FS

Alarm setpoint value SET1

ST2

0.0

Engineering unit*

6

-5 to +105 % FS

Alarm setpoint value SET2

PTn

1

N/A

1, 2, 3

Display pattern

2*

4

HYS1

1.0

Deviative engineering unit*

6

0 to 102 % FS

Deadband (hysteresis) for SET1

HYS2

1.0

Deviative engineering unit*

6

0 to 102 % FS

Deadband (hysteresis) for SET2

P-SL

0.0

Engineering unit*

6

-1999 to 9999

Scaling, lower range

P-SU

100.0

Engineering unit*

6

-1999 to 9999

Scaling, upper range

P-dP

1

N/A

0, 1, 2*

7

Decimal point position

P-A1

1

N/A

0 to 8

Alarm mode for SET1

P-A2

2

N/A

0 to 8

Alarm mode for SET2

P-d1

1

Seconds

1 to 999

Switching delay timer for SET1

P-d2

1

Seconds

1 to 999

Switching delay timer for SET2

3*

5

P-dF

5.0

Seconds

0.0 to 900.0

Time constant for the input filter

ADJ0

0.0

Deviative engineering unit*

6

-50 to +50 % FS

User’s ZERO adjustment

ADJS

0.0

Deviative engineering unit*

6

-50 to +50 % FS

User’s SPAN adjustment

P-d0

0

Seconds

0 to 20

Power ON delay time

REST

OFF

ON/OFF*

8

Resetting parameter

Ver

X.XX

Firmware version

*3. Pressing SEL key for 3 seconds turn the unit into setting mode for Parameter block 1.
*4. Pressing SEL key for 7 seconds turn the unit into setting mode for Parameter block 2.
*5. Pressing SEL key for 9 seconds turn the unit into setting mode for Parameter block 3.
*6.  Parameters set with “Engineering unit” or “Deviative engineering unit” shift according to changes in P-SL or P-SU setting 

regardless of the setting with ordering information sheet.

*7. 0 for no decimal point position, 1 for one-place decimal, 2 for two-place decimal.
*8.  3 sec. after REST to ON or by pressing SEL key, “Resetting parameter” is performed to reset parameters to default settings 

regardless of the setting with ordering information sheet.

Summary of Contents for KS2V3

Page 1: ...re change or condensation Corrosive gases sulfide and ammonia in particular or flammable gases Vibration or mechanical shock Direct contact with water oil chemical materials steam or vapor Exposure to...

Page 2: ...CONNECTION DIAGRAM 7 8 10 11 9 2 3 1 N C N O COM SET1 N C N O COM SET2 U V POWER INPUT 5 6 PANEL CUTOUT unit mm 45 45 0 5 0 0 5 0 85 MIN 63 MIN INSTALLATION Detach the yellow clamps located at the to...

Page 3: ...ET2 is in tripped conditions PREPARING POWER UP When the power is turned on the unit displays all segments on the Measured Value PV Alarm Setpoint Value SET1 Display and on the Alarm Setpoint Value SE...

Page 4: ...T1 P d2 1 Seconds 1 to 999 Switching delay timer for SET2 3 5 P dF 5 0 Seconds 0 0 to 900 0 Time constant for the input filter ADJ0 0 0 Deviative engineering unit 6 50 to 50 FS User s ZERO adjustment...

Page 5: ...Pat tern 2 Pattern 3 Upper blank Lower ST1 DOWN Press the key once Next parameter name is displayed Upper black Lower ST2 SEL Press the key once ST2 is replaced with current setting Upper blank Lower...

Page 6: ...atus or Operation Display Current display PTn 2 in this example Display pattern 2 Upper PV Lower blank SEL Keep pressing the key for 7 seconds Maintain while the display indicates Pat tern 2 Pattern 3...

Page 7: ...for 3 sec Upper blank Lower 6 SEL Press the key once The lower display indicates the param eter name P A2 again Upper blank Lower P A2 SEL Keep pressing the key for 3 seconds Maintain while the displ...

Page 8: ...ame ADJ0 again Upper blank Lower ADJ0 SEL Keep pressing the key for 3 seconds Maintain while the display changes Display pattern 1 Upper ST1 setpoint Lower ST2 setpoint User s SPAN adjustment Example...

Page 9: ...Low alarm With the function the unit is NOT tripped until the input goes once above and then below the setpoint ERROR MESSAGES DISPLAY ERROR DESCRIPTION WHAT TO DO UUUU The input exceeds 105 Return th...

Reviews: