KS2TR2
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-3606 Rev.5 P. 8 / 10
■
HOW TO SET PARAMETER BLOCK 3
Press SEL key for 9 seconds until the display turns to the
setting mode for Parameter block 3.
Time constant for the input filter
[Example]
Changing time constant for the input filter
(P-dF) from 5.0 sec. to 10.0 sec.
Key
Status or Operation
Display
Current display
(PTn = 1 in this example)
Display pattern 1
Upper = ST1 (setpoint)
Lower = ST2 (setpoint)
SEL
Keep pressing the key for 9 seconds.
→
Maintain while the display indicates Pat-
tern 2, Pattern 3, and Parameter block 1, 2,
until P-dF is on the display.
Upper = blank
Lower = P-dF
SEL
Press the key once.
→
P-dF is replaced with current setting.
Upper = blank
Lower = 5.0
UP
DOWN
Press the keys until the display indicates 10.0.
(New value is registered if the unit is not
accessed for 3 seconds.)
Upper = blank
Lower = 10.0
SEL
Press the key once.
→
The lower display indicates the param-
eter name (P-dF) again.
Upper = blank
Lower = P-dF
SEL
Keep pressing the key for 3 seconds.
→
Maintain while the display changes.
Display pattern 1
Upper = ST1 (setpoint)
Lower = ST2 (setpoint)
Cold junction compensation
[Example]
Changing cold junction compensation (CJM) ON
(internal) to OFF (external).
Key
Status or Operation
Display
Current display
(PTn = 1 in this example)
Display pattern 1
Upper = ST1 (setpoint)
Lower = ST2 (setpoint)
SEL
Keep pressing the key for 9 seconds.
→
Maintain while the display indicates Pat-
tern 2, Pattern 3, and Parameter block 1, 2,
until P-dF is on the display.
Upper = blank
Lower = P-dF
DOWN Press the key once.
→
Next parameter name is displayed.
Upper = blank
Lower = CJM
SEL
Press the key once.
→
CJM is replaced with current setting.
Upper = blank
Lower = ON
UP
DOWN
Press the keys until the display indicates OFF.
(New value is registered if the unit is not
accessed for 3 sec.)
Upper = blank
Lower = OFF
SEL
Press the key once.
→
The lower display indicates the param-
eter name (CJM) again.
Upper = blank
Lower = CJM
SEL
Keep pressing the key for 3 seconds.
→
Maintain while the display changes.
Display pattern 1
Upper = ST1 (setpoint)
Lower = ST2 (setpoint)
User’s ZERO adjustment
[Example]
Calibrate display value with 0% input (ADJ0) from 2 to 0.
ADJ0: 0
→
-2
Key
Status or Operation
Display
Current display
(PTn = 1 in this example)
Display pattern 1
Upper = ST1 (setpoint)
Lower = ST2 (setpoint)
SEL
Keep pressing the key for 9 seconds.
→
Maintain while the display indicates Pat-
tern 2, Pattern 3, and Parameter block 1, 2,
until P-dF is on the display.
Upper = blank
Lower = P-dF
DOWN Press the key twice.
→
Next parameter name is displayed.
Upper = blank
Lower = ADJ0
SEL
Press the key once.
→
ADJ0 is replaced with current setting.
Upper = blank
Lower = 0
UP
DOWN
Press the keys until the display indicates -2.
(New value is registered if the unit is not
accessed for 3 sec.)
Upper = blank
Lower = -2
SEL
Press the key once.
→
The lower display indicates the param-
eter name (ADJ0) again.
Upper = blank
Lower = ADJ0
SEL
Keep pressing the key for 3 seconds.
→
Maintain while the display changes.
Display pattern 1
Upper = ST1 (setpoint)
Lower = ST2 (setpoint)
User’s SPAN adjustment
[Example]
Calibrate display value with 100% input (ADJS)
from 99 to 100.
ADJS: 0
→
1
Key
Status or Operation
Display
Current display
(PTn = 1 in this example)
Display pattern 1
Upper = ST1 (setpoint)
Lower = ST2 (setpoint)
SEL
Keep pressing the key for 9 seconds.
→
Maintain while the display indicates Pat-
tern 2, Pattern 3, and Parameter block 1, 2,
until P-dF is on the display.
Upper = blank
Lower = P-dF
DOWN Press the key three times.
→
Next parameter name is displayed.
Upper = blank
Lower = ADJS
SEL
Press the key once.
→
ADJS is replaced with current setting.
Upper = blank
Lower = 0
UP
DOWN
Press the keys until the display indicates 1.
(New value is registered if the unit is not
accessed for 3 sec.)
Upper = blank
Lower = 1
SEL
Press the key once.
→
The lower display indicates the param-
eter name (ADJS) again.
Upper = blank
Lower = ADJS
SEL
Keep pressing the key for 3 seconds.
→
Maintain while the display changes.
Display pattern 1
Upper = ST1 (setpoint)
Lower = ST2 (setpoint)
Power ON delay time (P-d0)
[Example]
Changing power ON delay time (the time interval for the
alarm outputs to be enabled after the power is turned on.)
from 0 sec. to 3 sec.
Key
Status or Operation
Display
Current display
(PTn = 1 in this example)
Display pattern 1
Upper = ST1 (setpoint)
Lower = ST2 (setpoint)
SEL
Keep pressing the key for 9 seconds.
→
Maintain while the display indicates Pat-
tern 2, Pattern 3, and Parameter block 1, 2,
until P-dF is on the display.
Upper = blank
Lower = P-dF
DOWN Press the key four times.
→
Next parameter name is displayed.
Upper = blank
Lower = P-d0
SEL
Press the key once.
→
P-d0 is replaced with current setting.
Upper = blank
Lower = 0
UP
DOWN
Press the keys until the display indicates 3.
(New value is registered if the unit is not
accessed for 3 sec.)
Upper = blank
Lower = 3
SEL
Press the key once.
→
The lower display indicates the param-
eter name (P-d0) again.
Upper = blank
Lower = P-d0
SEL
Keep pressing the key for 3 seconds.
→
Maintain while the display changes.
Display pattern 1
Upper = ST1 (setpoint)
Lower = ST2 (setpoint)