DEFAULT PARAMETER SETTING

Param.
Block

Name

Default setting Unit

Programmable range

Explanations of function

1*

3

ST1

1200

Engineering unit*

6

-5 to +105 % FS

Alarm setpoint value SET1

ST2

0

Engineering unit*

6

-5 to +105 % FS

Alarm setpoint value SET2

PTn

1

N/A

1, 2, 3

Display pattern

2*

4

HYS1

1

Deviative engineering unit*

6

0 to 102 % FS

Deadband (hysteresis) for SET1

HYS2

1

Deviative engineering unit*

6

0 to 102 % FS

Deadband (hysteresis) for SET2

P-n2

3

N/A

0 to 8, 12 to 14

Input type

P-SL

0

Engineering unit*

6

-1999 to 9999

Scaling, lower range

P-SU

1200

Engineering unit*

6

-1999 to 9999

Scaling, upper range

P-dP

0

N/A

0 to 1 

Decimal point position

P-A1

1

N/A

0 to 8

Alarm mode for SET1

P-A2

2

N/A

0 to 8

Alarm mode for SET2

bUrn

H

N/A

H/L/norm

Burnout protection 
(upscale or downscale)

P-F

°C

°C/°F

°C/°F

Temperature unit

P-d1

1

Seconds

1 to 999

Switching delay timer for SET1

P-d2

1

Seconds

1 to 999

Switching delay timer for SET2

3*

5

P-dF

5.0

Seconds

5.0 to 900.0*

7

Time constant for the input filter

CJM

ON

ON/OFF

ON/OFF

Cold junction compensation

ADJ0

0

Deviative engineering unit*

6

-50 to +50 % FS

User’s ZERO adjustment

ADJS

0

Deviative engineering unit*

6

-50 to +50 % FS

User’s SPAN adjustment

P-d0

0

Seconds

0 to 20

Power ON delay time

REST

OFF

ON/OFF*

8

Resetting parameter

Ver

X.XX

Firmware version

*3. Pressing SEL key for 3 seconds turn the unit into setting mode for Parameter block 1.
*4. Pressing SEL key for 7 seconds turn the unit into setting mode for Parameter block 2.
*5. Pressing SEL key for 9 seconds turn the unit into setting mode for Parameter block 3.
*6. Parameters set with “Engineering unit” or “Deviative engineering unit” shift according to changes in P-SL or P-SU setting.
*7. Be sure to set at the minimum of 5.0 or a larger value though the unit accepts one smaller than 5.0.
*8.  3 sec. after REST to ON or by pressing SEL key, “Resetting parameter” is performed to reset parameters to default settings 

regardless of the setting with ordering information sheet.

Summary of Contents for KS2TR2

Page 1: ...H Rapid temperature change or condensation Corrosive gases sulfide and ammonia in particular or flammable gases Vibration or mechanical shock Direct contact with water oil chemical materials steam or vapor Exposure to air containing heavy dust particles salt chemical components or iron particles Interference by static and magnetic noise Direct sunlight Heat accumulated by radiation or such 2 Mount...

Page 2: ...DIAGRAM B B A 7 8 10 11 9 2 3 1 4 5 6 N C N O COM SET1 N C N O COM SET2 U V POWER RTD THERMOCOUPLE comp leadwire T C PANEL CUTOUT unit mm 45 45 0 5 0 0 5 0 85 MIN 63 MIN INSTALLATION Detach the yellow clamps located at the top and bottom of the unit for separate the body from the base socket DIN RAIL MOUNTING Set the base socket so that its DIN rail adaptor is at the bot tom Position the upper hoo...

Page 3: ... SET2 is in tripped conditions PREPARING POWER UP When the power is turned on the unit displays all segments on the Measured Value PV Alarm Setpoint Value SET1 Display and on the Alarm Setpoint Value SET2 Parameter Display before starting operation To ensure a proper operation of the unit set the parameters before starting up according to the operating conditions Be sure to remove power of the fin...

Page 4: ...unit P d1 1 Seconds 1 to 999 Switching delay timer for SET1 P d2 1 Seconds 1 to 999 Switching delay timer for SET2 3 5 P dF 5 0 Seconds 5 0 to 900 0 7 Time constant for the input filter CJM ON ON OFF ON OFF Cold junction compensation ADJ0 0 Deviative engineering unit 6 50 to 50 FS User s ZERO adjustment ADJS 0 Deviative engineering unit 6 50 to 50 FS User s SPAN adjustment P d0 0 Seconds 0 to 20 P...

Page 5: ...es Pat tern 2 Pattern 3 Upper blank Lower ST1 DOWN Press the key once Next parameter name is displayed Upper black Lower ST2 SEL Press the key once ST2 is replaced with current setting Upper blank Lower 100 UP DOWN Press the keys until the display indicates 50 New value is registered if the unit is not accessed for 3 seconds Upper blank Lower 50 SEL Press the key once The lower display indicates t...

Page 6: ...setting Upper blank Lower 3 UP DOWN Press the keys until the display indicates 2 New value is registered if the unit is not accessed for 3 sec Upper blank Lower 2 SEL Press the key once The lower display indicates the param eter name P n2 again Upper blank Lower P n2 SEL Keep pressing the key for 3 seconds Maintain while the display changes Display pattern 2 Upper PV Lower blank Scaling P SL P SU ...

Page 7: ...ew value is registered if the unit is not accessed for 3 seconds Upper blank Lower H SEL Press the key once The lower display indicates the param eter name bUrn again Upper blank Lower bUrn SEL Keep pressing the key for 3 seconds Maintain while the display changes Display pattern 1 Upper ST1 setpoint Lower ST2 setpoint Temperature unit Example Changing temperature unit P F from C to F Key Status o...

Page 8: ...ndicates Pat tern 2 Pattern 3 and Parameter block 1 2 until P dF is on the display Upper blank Lower P dF DOWN Press the key twice Next parameter name is displayed Upper blank Lower ADJ0 SEL Press the key once ADJ0 is replaced with current setting Upper blank Lower 0 UP DOWN Press the keys until the display indicates 2 New value is registered if the unit is not accessed for 3 sec Upper blank Lower...

Page 9: ... 4172 N N ALARM MODE v s PARAMETER CODE NO Param code P A1 P A2 Alarm modes Trip operation Set value Latching hold 9 Relay LED behavior in tripped conditions 0 No alarm 1 High Absolute value Without LED ON Coil energized 2 Low Absolute value Without LED ON Coil energized 3 High Absolute value With LED ON Coil energized 4 Low Absolute value With LED ON Coil energized 5 High Absolute value Without L...

Page 10: ... info m system co jp EM 3606 Rev 5 P 10 10 CHARACTER SET 0 1 2 4 3 5 6 7 9 8 A B D C E F G I H J K L N M O P Q S R T U V W X Z Y LIGHTNING SURGE PROTECTION M System offers a series of lightning surge protector for protection against induced lightning surges Please contact M System to choose appropriate models ...

Reviews: