KS2TR2

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-3606  Rev.5  P. 6 / 10

 

HOW TO SET PARAMETER BLOCK 2

Press SEL key for 7 seconds until the display turns to the setting mode for Parameter block 2.

Deadband (hysteresis) for SET1
[Example]

Changing deadband (hysteresis) (HYS1) for SET1 from 1 to 5.

Key

Status or Operation

Display

Current display
(PTn = 3 in this example)

Display pattern 3
Upper = blank
Lower = blank

SEL

Keep pressing the key for 7 seconds.

Maintain while the display indicates Pat-

tern 2, Pattern 3, and Parameter block 1, 
until HYS1 is on the display.

Upper = blank
Lower = HYS1

SEL

Press the key once.  

HYS1 is replaced with current seting.

Upper = blank
Lower = 1

UP

DOWN

Press the keys until the display indicates 5.
(New value is registered if the unit is not 
accessed for 3 sec.)

Upper = blank
Lower = 5

SEL

Press the key once.

The lower display indicates the param-

eter name (HYS1) again.

Upper = blank
Lower = HYS1

SEL

Keep pressing the key for 3 seconds.

Maintain while the display changes.

Display pattern 3
Upper = blank
Lower = blank

Deadband (hysteresis) for SET2
[Example]

Changing deadband (hysteresis) (HYS2) for SET2 from 1 to 3.

Key

Status or Operation

Display

Current display
(PTn = 3 in this example)

Display pattern 3
Upper = blank
Lower = blank

SEL

Keep pressing the key for 7 seconds.

Maintain while the display indicates Pat-

tern 2, Pattern 3, and Parameter block 1, 
until HYS1 is on the display.

Upper = blank
Lower = HYS1

DOWN Press the key once.

Next parameter name is displayed.

Upper = blank
Lower = HYS2

SEL

Press the key once.

HYS2 is replaced with current setting.

Upper = blank
Lower = 1

UP

DOWN

Press the keys until the display indicates 3.
(New value is registered if the unit is not 
accessed for 3 sec.)

Upper = blank
Lower = 3

SEL

Press the key once.

The lower display indicates the param-

eter name (HYS2) again.

Upper = blank
Lower = HYS2

SEL

Keep pressing the key for 3 seconds.

Maintain while the display changes.

Display pattern 3
Upper = blank
Lower = blank

Input type
[Example]

 Changing input type (P-n2) from K (3) to J (2).

Key

Status or Operation 

Display

Current display 
(PTn = 2 in this example) 

Display pattern 2
Upper = PV
Lower = blank

SEL

Keep pressing the key for 7 seconds. 

Maintain while the display indicates 2, 

Pattern 3, and Parameter block 1, until 
HYS1 is on the display.

Upper = blank
Pattern Lower = 
HYS1

DOWN  Press the key twice. 

Next parameter name is displayed. 

Upper = blank
Lower = P-n2

SEL

Press the key once. 

P-n2 is replaced with current setting. 

Upper = blank
Lower = 3

UP 

DOWN 

Press the keys until the display indicates 2.
(New value is registered if the unit is not 
accessed for 3 sec.)

 Upper = blank
Lower = 2

SEL 

Press the key once. 

The lower display indicates the param-

eter name (P-n2) again.

Upper = blank
Lower = P-n2

SEL 

Keep pressing the key for 3 seconds. 

Maintain while the display changes. 

Display pattern 2
Upper = PV
Lower = blank

Scaling (P-SL, P-SU)
[Example]

Changing scale (input range) from 0 – 400 to -100 – 200.

Key

Status or Operation

Display

Current display
(PTn = 2 in this example)

Display pattern 2
Upper = PV
Lower = blank

SEL

Keep pressing the key for 7 seconds.

Maintain while the display indicates Pat-

tern 2, Pattern 3, and Parameter block 1, 
until HYS1 is on the display.

Upper = blank
Lower = HYS1

DOWN Press the key three times.

Next parameter name is displayed.

Upper = blank
Lower = P-SL

SEL

Press the key once.

P-SL is replaced with current setting.

Upper = blank
Lower = 0

UP

DOWN

Press the keys until the display indicates 
-100. (New value is registered if the unit is 
not accessed for 3 sec.)

Upper = blank
Lower = -100

SEL

Press the key once.

The lower display indicates the param-

eter name (P-SL) again.

Upper = blank
Lower = P-SL

DOWN Press the key once.

Next parameter name is displayed.

Upper = blank
Lower = P-SU

SEL

Press the key once.

P-SU is replaced with current setting.

Upper = blank
Lower = 400

UP

DOWN

Press the keys until the display indicates 200.
(New value is registered if the unit is not 
accessed for 3 sec.)

Upper = blank
Lower = 200

SEL

Press the key once.

The lower display indicates the param-

eter name (P-SU) again.

Upper = blank
Lower = P-SU

SEL

Keep pressing the key for 3 seconds.

Maintain while the display changes.

Display pattern 2
Upper = PV
Lower = blank

[Example]

Changing decimal point position (P-dP) from XXX to XXX.X.

Key

Status or Operation

Display

Current display
(PTn = 2 in this example)

Display pattern 2
Upper = PV
Lower = blank

SEL

Keep pressing the key for 7 seconds.

Maintain while the display indicates Pat-

tern  2, Pattern 3, and Parameter block 1, 
until HYS1 is on the display.

Upper = blank
Lower = HYS1

DOWN Press the key five times.

Next parameter name is displayed.

Upper = blank
Lower = P-dP

SEL

Press the key once.

P-dP is replaced with current setting.

Upper = blank
Lower = 0

UP

DOWN

Press the keys until the display indicates 1.
(New value is registered if the unit is not 
accessed for 3 sec.)

Upper = blank
Lower = 1

SEL

Press the key once.

The lower display indicates the param-

eter name (P-dP) again.

Upper = blank
Lower = P-dP

SEL

Keep pressing the key for 3 seconds.

Maintain while the display changes.

Display pattern 2
Upper = PV
Lower = blank

 

SETPOINT v.s. DECIMAL POINT POSITION

Code

Decimal point position

Notes

0

XXXX

No decimal point

1

XXX.X

One-place decimal

Summary of Contents for KS2TR2

Page 1: ...H Rapid temperature change or condensation Corrosive gases sulfide and ammonia in particular or flammable gases Vibration or mechanical shock Direct contact with water oil chemical materials steam or vapor Exposure to air containing heavy dust particles salt chemical components or iron particles Interference by static and magnetic noise Direct sunlight Heat accumulated by radiation or such 2 Mount...

Page 2: ...DIAGRAM B B A 7 8 10 11 9 2 3 1 4 5 6 N C N O COM SET1 N C N O COM SET2 U V POWER RTD THERMOCOUPLE comp leadwire T C PANEL CUTOUT unit mm 45 45 0 5 0 0 5 0 85 MIN 63 MIN INSTALLATION Detach the yellow clamps located at the top and bottom of the unit for separate the body from the base socket DIN RAIL MOUNTING Set the base socket so that its DIN rail adaptor is at the bot tom Position the upper hoo...

Page 3: ... SET2 is in tripped conditions PREPARING POWER UP When the power is turned on the unit displays all segments on the Measured Value PV Alarm Setpoint Value SET1 Display and on the Alarm Setpoint Value SET2 Parameter Display before starting operation To ensure a proper operation of the unit set the parameters before starting up according to the operating conditions Be sure to remove power of the fin...

Page 4: ...unit P d1 1 Seconds 1 to 999 Switching delay timer for SET1 P d2 1 Seconds 1 to 999 Switching delay timer for SET2 3 5 P dF 5 0 Seconds 5 0 to 900 0 7 Time constant for the input filter CJM ON ON OFF ON OFF Cold junction compensation ADJ0 0 Deviative engineering unit 6 50 to 50 FS User s ZERO adjustment ADJS 0 Deviative engineering unit 6 50 to 50 FS User s SPAN adjustment P d0 0 Seconds 0 to 20 P...

Page 5: ...es Pat tern 2 Pattern 3 Upper blank Lower ST1 DOWN Press the key once Next parameter name is displayed Upper black Lower ST2 SEL Press the key once ST2 is replaced with current setting Upper blank Lower 100 UP DOWN Press the keys until the display indicates 50 New value is registered if the unit is not accessed for 3 seconds Upper blank Lower 50 SEL Press the key once The lower display indicates t...

Page 6: ...setting Upper blank Lower 3 UP DOWN Press the keys until the display indicates 2 New value is registered if the unit is not accessed for 3 sec Upper blank Lower 2 SEL Press the key once The lower display indicates the param eter name P n2 again Upper blank Lower P n2 SEL Keep pressing the key for 3 seconds Maintain while the display changes Display pattern 2 Upper PV Lower blank Scaling P SL P SU ...

Page 7: ...ew value is registered if the unit is not accessed for 3 seconds Upper blank Lower H SEL Press the key once The lower display indicates the param eter name bUrn again Upper blank Lower bUrn SEL Keep pressing the key for 3 seconds Maintain while the display changes Display pattern 1 Upper ST1 setpoint Lower ST2 setpoint Temperature unit Example Changing temperature unit P F from C to F Key Status o...

Page 8: ...ndicates Pat tern 2 Pattern 3 and Parameter block 1 2 until P dF is on the display Upper blank Lower P dF DOWN Press the key twice Next parameter name is displayed Upper blank Lower ADJ0 SEL Press the key once ADJ0 is replaced with current setting Upper blank Lower 0 UP DOWN Press the keys until the display indicates 2 New value is registered if the unit is not accessed for 3 sec Upper blank Lower...

Page 9: ... 4172 N N ALARM MODE v s PARAMETER CODE NO Param code P A1 P A2 Alarm modes Trip operation Set value Latching hold 9 Relay LED behavior in tripped conditions 0 No alarm 1 High Absolute value Without LED ON Coil energized 2 Low Absolute value Without LED ON Coil energized 3 High Absolute value With LED ON Coil energized 4 Low Absolute value With LED ON Coil energized 5 High Absolute value Without L...

Page 10: ... info m system co jp EM 3606 Rev 5 P 10 10 CHARACTER SET 0 1 2 4 3 5 6 7 9 8 A B D C E F G I H J K L N M O P Q S R T U V W X Z Y LIGHTNING SURGE PROTECTION M System offers a series of lightning surge protector for protection against induced lightning surges Please contact M System to choose appropriate models ...

Reviews: