TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on the front of the unit.
■
EXTERNAL DIMENSIONS unit: mm (inch)
3
4
5
6
2
1
8
7
80 (3.1
5)
50 (1.97)
103 (4.06)
123 (4.84)
[3.3 (.13)]
80 (3.1
5)
20 (.79)
40 (1.57)
50 (1.97)
7.8 (.31)
CLAMP
(top & bottom)
DIN RAIL
35mm wide
2
–
4.5 (.18) dia.
MTG HOLE
15 (.59) deep
8
–
M3.5
SCREW
• When mounting, no extra space is needed between units.
■
CONNECTION DIAGRAM
LOAD
SOURCE
l
k
L
K
+
–
OUTPUT
1
2
3
4
CONNECTOR
*
CLAMP-ON SENSOR
*
Connector provided only for the CLSA-08 and CLSA-12.
U(+)
V(–)
AUXILIARY POWER
7
8
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Auxiliary power input voltage: Check voltage across the
terminal 7 – 8 with a multimeter.
3) Input: Check that the input signal is within 0 – 100% of
the full-scale.
4) Output: Check that the load resistance meets the de-
scribed specifications.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.
■
HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of suffi-
cient accuracy level. Turn the auxiliary power supply on
and warm up for more than 10 minutes.
1) ZERO: Apply 0% input and adjust output to 0%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-
dure 1) – 3).
MAINTENANCE
Regular calibration procedure is explained below:
■
CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.