CHECKING

1)  Terminal wiring: Check that all cables are correctly con-

nected according to the connection diagram.

2)  DIP SW setting: Check that the switches are set to ap-

propriate positions.

3) Power input voltage: Check voltage across the terminal 

11 – 12 with a multimeter.

4)  Input: Check that the input signal is within 0 – 100% of 

full-scale.

5)  Output:  Check  that  the  load  resistance  meets  the  de

-

scribed specifications.

I/O RANGING & FINE ADJUSTMENTS

After the DIP SW setting is complete, set up the precise 
input and output range using the front control buttons.  Be 
sure that the front control button function is enabled with 
the DIP switch setting.
The front LEDs’ colors and blinking patterns help you to 
easily identify the transmitter’s status and confirm the set-
up actions in each step of Calibration Modes.  Please read 
the following explanations referring to “Calibration Flow 

Chart” below.

POWER ON

Amber LED

Green LED

Control
Buttons

Red LED

OFF

ON

Blink

RUN MODE

LD2

LD3

A

G

RUN MODE

LD2

LD3

G

R

LD1

LD2

LD3

LD1

LD2

LD3

0% INPUT

CONFIGURED

100% INPUT

CONFIGURED

INPUT

CALIBRATION

MODE

LD1

OUTPUT

CALIBRATION

MODE

LD2

LD3

LD1

LD2

LD3

0% OUTPUT

CONFIGURED

100% OUTPUT

CONFIGURED

G

G

R

R

R

R

G

R

R

G

Fine Adjustments ?

I/O Ranging ?

PUSH  

MODE

 

 1 – 2 s

PRESS & HOLD  

MODE

 

 > 5s

PUSH  

MODE

PUSH  

MODE

PUSH  

MODE

PUSH  

MODE

PUSH

DOWN

PUSH

UP

DOWN

UP

MODE

PUSH

DOWN

PUSH

UP

When you set 0% or 100% input/output ranges, 
keep pressing UP or DOWN button until the
LD1 blinks for approx. 2 seconds and turns off, 
which indicates the setup is complete.
When you release the button, the LD1 is returned
to ON.
If the LED does not change, the entered level may
be inappropriate, i.e. out of usable range.

FINE ZERO

CALIBRATION MODE

UP

  or  

DOWN

FINE SPAN

CALIBRATION MODE

UP

  or  

DOWN

Apply simulated 0% input signal.

Apply simulated 100% input signal.

Adjust simulated input until the output meter 
shows desired 0% output.

Adjust simulated input until the output meter 
shows desired 100% output.

*

1. Fine zero and calibrations are performed for 0% and 100% output regardless of the input value.

*

2

For the model M3LDY-x/A, the green LED is blinking.  For the model M3LDY-x/B, the green LED turns on.

*

1

*

1

LD1

*

2

LD1

*

2

 CALIBRATION FLOW CHART

Summary of Contents for Current Loop Supply M3LDY

Page 1: ...rs for the power source input and output connected to the unit COSEL Model NAC 04 472 TDK Model ZCAT 3035 1330 or equivalent is recommended Install lightning surge protectors for those wires connect e...

Page 2: ...NG Set the unit so that its DIN rail adaptor is at the bottom Position the upper hook at the rear side of the unit on the DIN rail and push in the lower When removing the unit push down the DIN rail a...

Page 3: ...ting no extra space is needed between units DIN RAIL 35mm wide EXTERNAL INTERNAL VIEWS 8 7 6 5 4 3 2 1 ON OFF ON OFF 4 3 2 1 Configuration DIP SW 10 11 12 7 8 9 4 5 6 1 2 3 Configurator Jack DOWN Butt...

Page 4: ...mable features can be set up on a PC regardless of other DIP SW setting except that the output type must be selected with the DIP SW1 1 through SW1 4 See Table 6 For detailed information on the PC con...

Page 5: ...ntrol Buttons Red LED OFF ON Blink RUN MODE LD2 LD3 A G RUN MODE LD2 LD3 G R LD1 LD2 LD3 LD1 LD2 LD3 0 INPUT CONFIGURED 100 INPUT CONFIGURED INPUT CALIBRATION MODE LD1 OUTPUT CALIBRATION MODE LD2 LD3...

Page 6: ...t level e g 1V Push DOWN button until the LD1 blinks for approx 2 sec and then turns OFF When you release the button the LD1 is returned to ON 7 100 Output Ranging Increase or decrease the simu lated...

Page 7: ...tion RUN Mode Option A The transmitter is configured via PC and is in normal operating conditions DIP SW Configuration RUN Mode The transmitter is configured via DIP SW and is in normal operating cond...

Reviews: