FRONT VIEW & PROGRAMMING

 PROGRAMMING PROCEDURE

1)  Press ITEM UP or DOWN key until ITEM display indicates “01”.
2)  Press  DATA  UP  or  DOWN  key  and  choose “1”  or “2”  on  DATA 

display.

   

1 : Only alarm setpoints are modifiable.

   

2 : All parameters are modifiable.

3)  Press  ITEM  UP  or  DOWN  key  until  ITEM  display  shows  the 

ITEM No. you need to change.

4)  Press DATA UP or DOWN key and choose a DATA No. or value 

you need on DATA display.

5)  Repeat above 3 and 4.  (Entered data is stored when you move to 

a new ITEM.)

6)  Press ITEM UP or DOWN key until ITEM display indicates “01”.
7)  Press DATA UP or DOWN key and choose “0” on the display.
8)  Press ITEM UP or DOWN key until ITEM display indicates “P”.  

DATA display shows process input.

  (You can now check data setting by choosing ITEM No.)
Note: DO NOT press UP and DOWN keys simultaneously.

L1

L2

L3

L4

ALARM

DATA

ITEM

DATA

ITEM

ITEM No. Display

DATA UP-DOWN Keys

ITEM No. UP-DOWN Keys

*

Monitor LEDs

DATA Display

*

L3 or L4 does not turn on for dual output type.

ITEM

MDF.

 

CODE

DATA

CONTENTS

DEFAULT SETTING

P

N/A

-1999 – 9999

Process input display in engineering unit (as set in ITEM 07/08)

----

L1

L2

L3

L4

1, 2

1, 2

1, 2

1, 2

-1999 – 9999*

1

-1999 – 9999*

1

-1999 – 9999*

1

-1999 – 9999*

1

L1 alarm setpoint in engineering unit

L2 alarm setpoint in engineering unit

L3 alarm setpoint in engineering unit *

2

L4 alarm setpoint in engineering unit *

2

Quad: 20.0   Dual: 20.0

Quad: 30.0   Dual: 80.0

Quad: 70.0

Quad: 80.0

01

0, 1, 2

Modification code

0 : Data indication only.

1 : Only ITEM L1 – L4 are modifiable.

2 : All parameters are modifiable.

1

02

N/A

Status indication (“0” is normally indicated.)

0: Normal  1: Memory error  10: Out of input range -15 – 115%

03

N/A

5

Input type

5: Potentiometer

04

N/A

-15.0 – 115.0

Input indicated in % (as set in ITEM27, 28)

----

05

06

2

2

-19.99 – 99.99

0.000 – 9.999

Zero adjustment (%) (fine adj. of the value set in ITEM 27)

0.00

Gain adjustment (fine adj. of the value set in ITEM 28)

1.000

07

08

2

2

-1999 – 9999

-1999 – 9999

Display range scaling     0% *

3

Display range scaling 100% *

3

0.0

100.0

09

2

0, 1, 2, 3

Decimal point 

position

(Specify the 

number of 

digits) 

0 : _ _ _ _

1 : _ _ _ . _

2 : _ _ . _ _

3 : _ . _ _ _

1

10

2

0 – 99

Power ON-delay time (seconds)

5

11

2

0 – 999

Alarm ON-delay time (seconds)

0

12

2

0, 1, 2, 3, 4

Moving average (sampling cycle: 100 msec.)

0: No, 1: 4 samples, 2: 8 samples, 3: 16 samples, 4: 32 samples

0

13

14

15

16

2

2

2

2

0, 1

0, 1

0, 1

0, 1

L1 trip operation 

L2 trip operation 

L3 trip operation 

L4 trip operation 

(0: Lo, 1: Hi)

(0: Lo, 1: Hi)

(0: Lo, 1: Hi) *

2

(0: Lo, 1: Hi) *

2

Quad: 0

Quad: 0

Quad: 1

Quad: 1

Dual: 0

Dual: 1

17

2

-1, 0, 1 – 60

Power-saving mode

-1 : Continuous display upon startup

0 : Continuous display after the last access

1 – 60: Time before display turned off (minutes)

0: Continuous display

18

19

20

21

2

2

2

2

0, 1

0, 1

0, 1

0, 1

L1 coil at alarm    (0: Energized, 1: De-energized)

L2 coil at alarm     (0: Energized, 1: De-energized)

L3 coil at alarm     (0: Energized, 1: De-energized)*

2

L4 coil at alarm     (0: Energized, 1: De-energized)*

2

0

0

0

0

22

N/A

----

Version No. indication

----

23

24

25

26

2

2

2

2

1 – 9999

1 – 9999

1 – 9999

1 – 9999

L1 hysteresis (deadband) in engineering unit

L2 hysteresis (deadband) in engineering unit

L3 hysteresis (deadband) in engineering unit *

2

L4 hysteresis (deadband) in engineering unit *

2

1.0

1.0

1.0

1.0

Summary of Contents for AS4M

Page 1: ...level of this unit when it is integrated in a panel system The user may have to review the CE re quirements in regard to the whole system and employ ad ditional protective measures to ensure the CE conformity POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 100 240V AC rating 85 264V 47 66 Hz approx 6VA 10...

Page 2: ...01 0 1 2 Modification code 0 Data indication only 1 Only ITEM L1 L4 are modifiable 2 All parameters are modifiable 1 02 N A 0 Status indication 0 is normally indicated 0 Normal 1 Memory error 10 Out of input range 15 115 03 N A 5 Input type 5 Potentiometer 04 N A 15 0 115 0 Input indicated in as set in ITEM27 28 05 06 2 2 19 99 99 99 0 000 9 999 Zero adjustment fine adj of the value set in ITEM 27...

Page 3: ... 100 input 4 Alarm operations Check the alarm operations referring to the figure below 5 Output load Check that the output load is 380V AC 120VA or 125V DC 30W 380V AC 600VA or 125V DC 150W for dual alarm Output Code 5 at the maxi mum For maximum relay life with inductive load ex ternal protection is recommended 0 50 100 Input LL L HH H L2 1 2 ON L3 1 3 ON L4 9 11 ON OFF OFF L1 9 10 ON OFF OFF Ala...

Page 4: ...igher than the set point and check that the relay trips at the L or LL setpoint within the setpoint accuracy described in the data sheet When the setpoints are shifted please contact M System s Sales Office or representatives LIGHTNING SURGE PROTECTION In order to protect the unit from lightning surges entering through power supply cables use of appropriate lightning surge protectors are recommend...

Reviews: