MAINTENANCE

Regular calibration procedure is explained below:

 CALIBRATION

Warm up the unit for at least 10 minutes.

• H (HH) Setpoint

Increase the input signal from a value lower than the set-

point and check that the relay trips at the H (or HH) set

-

point within the setpoint accuracy described in the data 
sheet.

• L (LL) Setpoint

Decrease the input signal from a value higher than the set

-

point and check that the relay trips at the L (or LL) setpoint 
within the setpoint accuracy described in the data sheet.

When the setpoints are shifted, please contact M-System’s 

Sales Office or representatives.

LIGHTNING SURGE PROTECTION

In order to protect the unit from lightning surges entering 
through power supply cables, use of appropriate lightning 
surge protectors are recommended.  Please contact M-Sys-
tem.

EXTERNAL DIMENSIONS

  unit: mm (inch)

80 (3.15)

50 (1.97)

103 (4.06)

132 (5.20)

20 (.79)

• When mounting, no extra space is needed between units.

5

6

7

8

2

1

11

10

[3.3 (.13)]

80 (3.15)

35.4 (1.39)

40 (1.57)

50 (1.97)

7.8 (.31)

CLAMP

(top & bottom

)

DIN RAIL

35mm wide

2–4.5 (.18) dia.

MTG HOLE

25 (.98) deep

11–M3.5

SCRE

W

3

9

4

Summary of Contents for AS4M

Page 1: ...level of this unit when it is integrated in a panel system The user may have to review the CE re quirements in regard to the whole system and employ ad ditional protective measures to ensure the CE conformity POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 100 240V AC rating 85 264V 47 66 Hz approx 6VA 10...

Page 2: ...01 0 1 2 Modification code 0 Data indication only 1 Only ITEM L1 L4 are modifiable 2 All parameters are modifiable 1 02 N A 0 Status indication 0 is normally indicated 0 Normal 1 Memory error 10 Out of input range 15 115 03 N A 5 Input type 5 Potentiometer 04 N A 15 0 115 0 Input indicated in as set in ITEM27 28 05 06 2 2 19 99 99 99 0 000 9 999 Zero adjustment fine adj of the value set in ITEM 27...

Page 3: ... 100 input 4 Alarm operations Check the alarm operations referring to the figure below 5 Output load Check that the output load is 380V AC 120VA or 125V DC 30W 380V AC 600VA or 125V DC 150W for dual alarm Output Code 5 at the maxi mum For maximum relay life with inductive load ex ternal protection is recommended 0 50 100 Input LL L HH H L2 1 2 ON L3 1 3 ON L4 9 11 ON OFF OFF L1 9 10 ON OFF OFF Ala...

Page 4: ...igher than the set point and check that the relay trips at the L or LL setpoint within the setpoint accuracy described in the data sheet When the setpoints are shifted please contact M System s Sales Office or representatives LIGHTNING SURGE PROTECTION In order to protect the unit from lightning surges entering through power supply cables use of appropriate lightning surge protectors are recommend...

Reviews: