AD3V
P. 5 / 8 EM-1389 Rev.13
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
OUTPUT DATA & PARITY BIT RELATIONSHIP
Hi and Lo indicate the voltage level. Parity logic is unchanged.
■
OPEN COLLECTOR
■
CMOS
•Positive Logic I14 : 1, Lo : False, Hi: True
DATA
8
4
2
1
PARITY
Even I12 : 0
Odd I12 : 1
0
Lo
Lo
Lo
Lo
Lo
Hi
1
Lo
Lo
Lo
Hi
Hi
Lo
2
Lo
Lo
Hi
Lo
Hi
Lo
3
Lo
Lo
Hi
Hi
Lo
Hi
4
Lo
Hi
Lo
Lo
Hi
Lo
5
Lo
Hi
Lo
Hi
Lo
Hi
6
Lo
Hi
Hi
Lo
Lo
Hi
7
Lo
Hi
Hi
Hi
Hi
Lo
8
Hi
Lo
Lo
Lo
Hi
Lo
9
Hi
Lo
Lo
Hi
Lo
Hi
10
Hi
Lo
Hi
Lo
Lo
Hi
11
Hi
Lo
Hi
Hi
Hi
Lo
12
Hi
Hi
Lo
Lo
Lo
Hi
13
Hi
Hi
Lo
Hi
Hi
Lo
14
Hi
Hi
Hi
Lo
Hi
Lo
15
Hi
Hi
Hi
Hi
Lo
Hi
•Negative Logic I14 : 0, Lo : True, Hi: False
DATA
8
4
2
1
PARITY
Even I12 : 0
Odd I12 : 1
0
Hi
Hi
Hi
Hi
Lo
Hi
1
Hi
Hi
Hi
Lo
Hi
Lo
2
Hi
Hi
Lo
Hi
Hi
Lo
3
Hi
Hi
Lo
Lo
Lo
Hi
4
Hi
Lo
Hi
Hi
Hi
Lo
5
Hi
Lo
Hi
Lo
Lo
Hi
6
Hi
Lo
Lo
Hi
Lo
Hi
7
Hi
Lo
Lo
Lo
Hi
Lo
8
Lo
Hi
Hi
Hi
Hi
Lo
9
Lo
Hi
Hi
Lo
Lo
Hi
10
Lo
Hi
Lo
Hi
Lo
Hi
11
Lo
Hi
Lo
Lo
Hi
Lo
12
Lo
Lo
Hi
Hi
Lo
Hi
13
Lo
Lo
Hi
Lo
Hi
Lo
14
Lo
Lo
Lo
Hi
Hi
Lo
15
Lo
Lo
Lo
Lo
Lo
Hi
•Positive Logic I14 : 0, Lo : False, Hi: True
DATA
8
4
2
1
PARITY
Even I12 : 0
Odd I12 : 1
0
Lo
Lo
Lo
Lo
Hi
Lo
1
Lo
Lo
Lo
Hi
Lo
Hi
2
Lo
Lo
Hi
Lo
Lo
Hi
3
Lo
Lo
Hi
Hi
Hi
Lo
4
Lo
Hi
Lo
Lo
Lo
Hi
5
Lo
Hi
Lo
Hi
Hi
Lo
6
Lo
Hi
Hi
Lo
Hi
Lo
7
Lo
Hi
Hi
Hi
Lo
Hi
8
Hi
Lo
Lo
Lo
Lo
Hi
9
Hi
Lo
Lo
Hi
Hi
Lo
10
Hi
Lo
Hi
Lo
Hi
Lo
11
Hi
Lo
Hi
Hi
Lo
Hi
12
Hi
Hi
Lo
Lo
Hi
Lo
13
Hi
Hi
Lo
Hi
Lo
Hi
14
Hi
Hi
Hi
Lo
Lo
Hi
15
Hi
Hi
Hi
Hi
Hi
Lo
•Negative Logic I14 : 1, Lo : True, Hi: False
DATA
8
4
2
1
PARITY
Even I12 : 0
Odd I12 : 1
0
Hi
Hi
Hi
Hi
Hi
Lo
1
Hi
Hi
Hi
Lo
Lo
Hi
2
Hi
Hi
Lo
Hi
Lo
Hi
3
Hi
Hi
Lo
Lo
Hi
Lo
4
Hi
Lo
Hi
Hi
Lo
Hi
5
Hi
Lo
Hi
Lo
Hi
Lo
6
Hi
Lo
Lo
Hi
Hi
Lo
7
Hi
Lo
Lo
Lo
Lo
Hi
8
Lo
Hi
Hi
Hi
Lo
Hi
9
Lo
Hi
Hi
Lo
Hi
Lo
10
Lo
Hi
Lo
Hi
Hi
Lo
11
Lo
Hi
Lo
Lo
Lo
Hi
12
Lo
Lo
Hi
Hi
Hi
Lo
13
Lo
Lo
Hi
Lo
Lo
Hi
14
Lo
Lo
Lo
Hi
Lo
Hi
15
Lo
Lo
Lo
Lo
Hi
Lo
FRONT PANEL CONFIGURATION & PROGRAMMING
■
PROGRAMMING PROCEDURE
1) Press ITEM UP or DOWN key until ITEM display indicates “01”.
2) Press DATA UP or DOWN key and choose “2” on DATA display.
1 : Data indication only.
2 : All parameters are modifiable.
3) Press ITEM UP or DOWN key until ITEM display shows the ITEM No.
you need to change.
4) Press DATA UP or DOWN key and choose a DATA No. or value you need
on DATA display.
5) Repeat above 3 and 4. (Entered data is stored when you move to a new
ITEM.)
6) Press ITEM UP or DOWN key until ITEM display indicates “01”.
7) Press DATA UP or DOWN key and choose “1” on the display.
8) Press ITEM UP or DOWN key until ITEM display indicates “P”.
DATA display shows process input. You can now check data setting by choosing ITEM No.
Note : DO NOT press UP and DOWN keys simultaneously.
DATA
ITEM
DATA
ITEM
ITEM
UP-DOWN Keys
PL2 (HOLD) LED
PL1 (POL) LED
DATA Display
ITEM Display
DATA
UP-DOWN Keys
26-pin Connector
(Pin Assignments)
1
2
25
26