ABF3
P. 2 / 5
EM-2614 Rev.5
INSTALLATION
■
PANEL CUTOUT unit: mm
Mounting Bracket
Panel thickness: 1.6 – 8.0 mm
• Single Mounting (ingress protection)
• Clustered Mounting (no ingress protection)
92
+ 0.8 – 0
92
+ 0.8 – 0
45
+ 0.6
– 0
Panel thickness: 1.6 – 8.0 mm
L = (45.5 + 48 x (N – 1))
(N : number of units)
+1
–0
L
Leave a minimum of 3 cm above and below the units
for heat dissipation.
■
HOW TO MOUNT THE UNIT ON A PANEL
1) Insert the unit into the panel cutout. The watertight
packing must be in place to hold the unit. Do not remove
it.
The IP protection is effective only with single mounting,
with the designated cutout size (45
×
92 mm).
2) Push the mounting brackets into the grooves on top and
bottom of the rear module, until they hit the panel’s rear
side.
TERMINAL CONNECTIONS
Refer to the connection diagrams below.
Panel
Watertight Packing