54UC
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6489-B Rev.9 P. 40 / 47
Change Setting
(SETTINGS)
Demand Setting
(DEMAND)
Energy Setting
(ENERGY)
Average current
(I)
DIN : External discrete input
1 thr. 60 : Minutes (30)
Average power
(POWER)
DIN : External discrete input
1 thr. 60 : Minutes (30)
Pulse output 1
(COUNT1)
*
4
Pulse weight 1
(WEIGHT1)
0.1 thr. 10 000.0 :
kWh / kvarh / kVAh (1.0)
Pulse width 1
(DURATION1)
100 thr. 2 000 ms (100 ms increments)
(100)
Tariff switching
(TARIFF)
DISABLE (
*
)
ENABLE
Pulse output 2
(COUNT2)
*
4
Pulse weight 2
(WEIGHT2)
0.1 thr. 10 000.0 :
kWh / kvarh / kVAh (1.0)
Pulse width 2
(DURATION2)
100 thr. 2 000 ms (100 ms increments)
(100)
(
*
) or ( ) : Factory setting
CC-Link setting
(CC-LINK)
Node address
(ADDRESS)
1 thr. 64 (1)
Baud rate
(BAUDRATE)
156 kbps / 625 kbps / 2.5 Mbps /
5 Mbps / 10 Mbps (
*
)
*
3
*
3. In order to make the settings effective, turn on the power again, or reboot the device or reset CC-Link by using buttons on the front panel.
*
4. Refer to "Energy count type" in "CC-Link - SETTING" section.
Change Setting
(SETTINGS)
Discrete I/O
Setting (DIO)
Discrete output 1 function
(DO1-FUNC)
NO FUNC : Not used (
*
)
ENERGY : Energy count pulse
ALARM : Alarm output
Discrete output 1 mode
(DO1-TYPE)
N-O : Normally open (
*
)
N-C : Normally closed
Discrete output 2 function
(DO2-FUNC)
NO FUNC : Not used (
*
)
ENERGY : Energy count pulse
ALARM : Alarm output
Discrete output 2 mode
(DO2-TYPE)
N-O : Normally open (
*
)
N-C : Normally closed
Discrete input function
(DIN-FUNC)
NO FUNC : Not used (
*
)
DEMAND : Update demand
RESET E : Reset energy
CLR ALARM : Reset alarm
TARIFF : Switch tariff
Discrete input type
(DIN-TYPE)
N-O : Normally open (
*
)
N-C : Normally closed
(
*
) or ( ) : Factory setting
DI
DI